1

Stredne ťažká

Why is ammonia (R717) classed as a toxic refrigerant?


It severely irritates the respiratory tract, eyes and skin, and is poisonous when inhaled at higher concentrations
Because it does not react with water, making neutralisation difficult
Because it is heavier than air and displaces oxygen
Because it is colourless and odourless and therefore hard to detect

2

Ťažká

What is the main difference between a dry-expansion and a flooded evaporator?


In a dry-expansion evaporator the refrigerant completely evaporates and is superheated in the evaporator; in a flooded one part of the refrigerant remains liquid (incomplete evaporation, no superheat)
A dry-expansion evaporator always has a lower pressure than a flooded one
A dry-expansion evaporator is filled with liquid, a flooded one with vapour
A dry-expansion evaporator needs no expansion valve, a flooded one does

3

Ťažká

What is the typical pressure in the evaporator of an R717 deep-freeze system (below −40 °C)?


Atmospheric pressure, approx. 1 bar abs
Below atmospheric (approx. 0.7 bar abs at −40 °C)
Positive pressure of 5–10 bar
Positive pressure of 10–20 bar

4

Ľahká

What is the basic requirement when charging a system with R717 (NH₃)?


NH₃ can be charged together with air
Charging should take place in a well-ventilated area using appropriate personal protective equipment
Charging must only take place at temperatures below 0°C
Charging can be carried out without personal protective equipment

5

Ťažká

How is oil managed in R717 systems?


Oil can be mixed with any refrigerant
Oil has no effect on system operation
Oil requires no monitoring
Oil collecting at the lowest points of vessels is regularly checked and drained, because it impairs heat transfer

6

Ľahká

What is the correct procedure for recovering R717 from a system?


Recovery is not required
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
The gas can be released into the atmosphere
The refrigerant can be drained into the sewer system

7

Ľahká

How should R717 (NH₃) be stored?


In unmarked plastic containers
Near heat sources
In sealed, labelled containers, in a cool and well-ventilated place
In any open containers

8

Ťažká

What should be done with contaminated R717?


Release it into the atmosphere
Purify it or send it for disposal in accordance with regulations
Continue to use it without restriction
Dilute it with water and reuse it

9

Ľahká

What is the main hazard associated with an R717 leak during maintenance work?


Increased cooling efficiency
No risk whatsoever
Damage to electrical equipment only
Toxic to humans and may cause chemical burns

10

Ťažká

What should be done if an NH₃ leak is detected?


Carry on working with the room door open
Increase the pressure in the system
Carry on working wearing a dust mask
Evacuate people immediately and raise the alarm; stop the leak only if it is safe to do so and with suitable PPE (respiratory protection)

11

Ťažká

What role do scrubbers play in NH₃ systems?


They increase the pressure in the system
Neutralise ammonia through absorption in a liquid (e.g. water)
They are used to measure temperature
They store the refrigerant

12

Ťažká

How should the system be prepared before filling with R717?


The pressure must be increased above the standard level
There is no need to check it
Check for leaks, remove air and moisture, and create a vacuum
Simply start it up

13

Ťažká

What are the transport requirements for R717?


It can be carried without labelling
It can be carried in open containers
Transport is not regulated
It must be carried in suitable, labelled packagings in accordance with ADR (UN 1005, class 2, code 2TC)

14

Ľahká

What personal protective equipment is required when working with NH₃?


Safety goggles, gloves and respiratory protective equipment
No requirements
Workwear only
Only a safety helmet

15

Ťažká

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 does not mix with the oil; the oil collects on the high-pressure side above the R717
R717 mixes very well with the oil, which easily returns to the compressor
R717 does not mix with the oil; the oil, being heavier than liquid NH₃, collects beneath it at the lowest points (mainly on the low-pressure side)
An oil return line cannot be used in R717 systems because the oil is too hot

16

Ťažká

Which refrigerant can be detected with phenolphthalein paper?


R1234ze(E)
R717
R1270
R744

17

Ťažká

Which system may require manual oil recovery?


An R717 system
Supercritical ‘booster’ system using R744
R744 cascade system
Secondary system using R744

18

Ťažká

Which refrigerant is lighter than air?


R1270
R744
R717
R1234ze(E)

19

Ťažká

R717 is highly corrosive to:


titanium
stainless steel
aluminium
copper (and its alloys)

20

Ťažká

What is the recommended pre-alarm level for fixed leak detection systems for R717?


500 ppm
5,000 ppm
500,000 ppm
50,000 ppm

21

Ťažká

Why are compressors with a separate motor (open type) mostly used in R717 systems?


To increase the refrigerant charge
Because they are cheaper
Because NH₃ attacks copper motor windings, so hermetic compressors with conventional windings are not used
To lower the condensing pressure

22

Ťažká

Which type of compressor is most commonly used in large ammonia systems?


A reciprocating or screw compressor
Diaphragm compressor
Rotary vane compressor
Hermetic scroll

23

Ťažká

How is the capacity of a piston compressor regulated in NH₃ systems?


By unloading the cylinders or changing the rotational speed
By reducing the refrigerant charge
By increasing the condensing pressure
Solely by adjusting the oil volume

24

Ťažká

How is the capacity of a screw compressor most commonly controlled?


By changing the type of oil
By closing the suction valve
By using a slide valve
By adjusting the oil level

25

Ťažká

When is two-stage compression used in NH₃ systems?


At small temperature differences
Only in small systems
At low evaporating temperatures (pressures) and high pressure ratios
Only with water-cooled condensers

26

Ťažká

What is the advantage of two-stage compression over single-stage compression?


No need for a separator
Higher energy consumption
Lower efficiency
Higher efficiency and lower discharge temperature

27

Ťažká

How does an evaporative condenser used in NH₃ systems work?


It transfers heat only to the air
It does not require a water supply
Operates without a fan
It utilises the evaporation of water to increase cooling efficiency

28

Ťažká

What is the function of the liquid separator in an NH₃ system?


It separates oil from the refrigerant
It prevents liquid from entering the compressor
Regulates the condensing pressure
Increases the discharge temperature

29

Ťažká

What is the purpose of monitoring the liquid level in the separator?


To control the condenser fan
To increase the oil volume
To reduce the condensing temperature
To maintain the correct refrigerant level and prevent the compressor from flooding

30

Ťažká

What is the role of the float switch in NH₃ systems?


It regulates the condensation temperature
It controls the fan’s operation
It is used to detect leaks
It monitors the liquid level in the tank or separator

31

Ťažká

What is a thermosyphon in NH₃ systems?


An oil circulation pump
A defrosting device
A type of safety valve
A system with gravity-driven (natural) circulation of liquid refrigerant caused by density differences, used e.g. for screw compressor oil cooling

32

Ťažká

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


To reduce the pressure
Because NH₃ does not mix with most compressor oils
Because the oil mixes only with water
To increase the amount of refrigerant

33

Ťažká

What is the main function of an oil separator in NH₃ systems?


To lower the condensation temperature
Removing moisture from the system
To separate the oil from the refrigerant and return the oil to the compressor
To increase fan efficiency

34

Ťažká

In which NH₃ system does the refrigerant evaporate completely with superheat in the evaporator, fed by an expansion valve?


An indirect system
A pumped liquid-recirculation system
A glycol system
A direct-expansion (DX) system

35

Ťažká

What is the characteristic feature of a flooded evaporator system?


The evaporator contains a large amount of liquid, which improves heat transfer
No level control is required
The evaporator is filled exclusively with vapour
No separator is used

36

Ťažká

What is the main difference between a direct and an indirect system?


In an indirect system, no compressor is used
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load
In an indirect system, NH₃ flows directly into the space being cooled
In a direct system, there is no evaporator

37

Stredne ťažká

Which property of ammonia helps people detect a leak early?


It is denser than air
A very low odour threshold (a few ppm)
It is odourless
It is yellow in air