F-Gas English Low GWP
All questions
HFC | Flammable | CO₂ | NH₃
Easy questions |
Medium questions |
Difficult questions
1
Easy
What is the base unit of mass according to the International System of Units (Système International d’Unités)?
| N |
| t |
| kg |
| Pound |
2
Medium
What process takes place in the condenser of a refrigeration system?
| In the condenser, the refrigerant releases the heat absorbed in the evaporator into the surroundings. |
| The medium flowing through the evaporator (glycol, water) condenses, whilst the refrigerant evaporates. |
| Hot refrigerant vapour is pumped from the compressor to the condenser, where it is cooled and then condensed. In this heat exchanger, the resulting liquid refrigerant is also slightly subcooled. |
| The refrigerant releases the heat absorbed in the compressor via the condenser |
3
Medium
What determines the condensation temperature of an air-cooled unit?
| On the superheat temperature. |
| On the evaporation (boiling) temperature. |
| On the ambient temperature. |
| On the compressor and discharge temperatures |
4
Medium
Is energy required when heat is transferred from the condenser to the surroundings?
| No, because according to the second law of thermodynamics, thermal energy always flows from a body at a higher temperature to a body at a lower temperature. |
| The heat flow balances the energy input. |
| Yes, in every case. |
| Yes, but only when using HFC refrigerants. |
5
Medium
What should you pay attention to during the operation of the condenser?
| Pay attention to the fan’s operation and the ambient temperature. |
| Ensure that the air temperature at the condenser outlet is higher than the condensation temperature. |
| You should ensure the general maintenance of the condenser and keep the heat exchange surfaces clean. |
| Care should be taken to ensure that the air temperature at the condenser inlet is lower than the air temperature at the condenser outlet. |
6
Medium
What criteria should be considered when selecting a suitable condenser?
| These include size and the number of fans. The geometric parameters of the condenser must be taken into account. |
| Condensers should be selected based on your own experience, and the condenser’s geometric parameters should be taken into account. |
| The required capacity of the condenser and the technical specifications declared by the manufacturer must be taken into account. |
| First and foremost, you should consider the operating noise level of the fans, the diameter of the connection pipes and the colour scheme. |
7
Medium
How do contaminants (dust, particulates, deposits) affect the performance and efficiency of heat exchange surfaces in condensers?
| Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause a reduction in condensing pressure. |
| Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause an increase in condensing temperature and pressure, which in turn leads to a reduction in the condenser’s efficiency. |
| Contaminants do not significantly affect the efficiency and effectiveness of the heat exchange surfaces in condensers. |
| Contaminants increase the heat transfer area and reduce the condensing pressure. |
8
Medium
If an air-cooled condenser becomes contaminated, will the condensation efficiency?
| It will decrease. |
| It remains unchanged. |
| It will increase. |
| It will increase as a result of the fan speed being raised further. |
9
Medium
What can cause frost to form on the evaporator?
| Frost build-up on the evaporator increases airflow resistance and, consequently, causes the fan motor to work harder. |
| A reduction in the temperature of the cooled substance. |
| a drop in cooling capacity. |
| An increase in refrigerant flow resistance and a reduction in the refrigerant flow rate through the evaporator. |
10
Medium
What happens when the evaporation temperature drops?
| The compressor’s cooling capacity decreases. |
| The compressor’s cooling capacity increases. |
| The condenser fan speed increases. |
| The discharge temperature decreases. |
11
Medium
When is defrosting using the refrigerant possible?
| In the case of air-cooled chillers, only when the air temperature is above 0°C. |
| Never. We use electricity for defrosting (for example, using a special electric heater). |
| Only when using speed-controlled fans. |
| Defrosting using the refrigerant is not possible at all. |
12
Medium
When can frost form on the evaporator surface?
| Frost always forms on air coolers. |
| Only in the case of air coolers, when the air temperature drops below 0°C. |
| In the case of finned evaporators. |
| Frost forms only when the refrigeration system is operating continuously. |
13
Medium
In the case of extensive pipework systems, secondary evaporation of the refrigerant can be prevented by...
| using larger-diameter pipes. |
| by insulating the pipes between the compressor and the condenser. |
| additional cooling. |
| using smaller-diameter pipes. |
14
Medium
How does hot gas defrosting of the evaporator work?
| We swap the outlet and inlet sides of the evaporator. |
| We switch on the gas heater directed at the evaporator. |
| This involves reversing the direction of rotation of the compressor. |
| Heated vapour (hot gas) from the compressor is directed into the evaporator piping. |
15
Medium
What is the function of the evaporator in a refrigeration system?
| Thanks to the evaporator, the cooled medium transfers heat to the boiling refrigerant. |
| It cools the refrigerant. |
| It evaporates the water flowing through the evaporator. |
| It ensures that the refrigerant is superheated over the largest possible heat exchange surface area. |
16
Medium
What conditions must be met for the evaporator to be defrosted using electric heaters?
| The electric heaters must be in contact with the evaporator’s heat exchange surface (the heater must touch the fins). |
| Thanks to the forced air flow created by the fans, the heat from the heaters is transferred to the heat exchanger. |
| The electric heaters must be positioned in direct contact with the refrigerant so that the refrigerant flowing through the evaporator is at a sufficiently high temperature. |
| The electric heaters must be positioned beneath the evaporator’s heat exchange surface. |
17
Medium
Refrigerant distributor:
| ensures an even distribution of the refrigerant to the individual sections of the evaporator. |
| ensures even distribution of the refrigerant to the individual sections of the condenser. |
| ensures the even distribution of the refrigerant discharged by compressors connected in parallel. |
| acts as a buffer for the refrigerant in the event that the pressure upstream of the expansion valve is exceeded. |
18
Medium
What are the possible methods of defrosting air coolers?
| Electric defrosting, liquid defrosting or defrosting using hot refrigerant vapour. |
| Electric defrosting only. |
| Natural defrosting; there are no other effective methods. |
| Hot gas defrosting. |
19
Medium
The boiling point increases (and consequently the rate of evaporation increases) if the pressure above the liquid...
| It behaves differently depending on the ambient temperature. |
| Rises. |
| Remains constant. |
| Falls. |
20
Medium
MOP in thermostatic expansion valves stands for:
| minimum flow opening. |
| self-cleaning of the valve in the event of moisture in the refrigerant freezing. |
| maximum operating pressure. |
| maximum pressure switch protection. |
21
Medium
The function of a thermostatic expansion valve (TEV) in a refrigeration system is:
| to consistently adjust the evaporation pressure in the condenser depending on the temperature of the refrigerant vapour leaving the condenser. |
| to maintain a constant suction pressure to the compressor. |
| regulating the superheat of the refrigerant leaving the evaporator so that it is at the minimum value. |
| to control the amount of refrigerant supplied to the evaporator depending on the superheat of the vapour leaving that heat exchanger. |
22
Medium
When using a capillary tube, what type of motor can be used in the compressor?
| A low-speed motor should be used. |
| A motor with low starting torque can be used. |
| An electronically commutated motor approved for use with the compressor should be used. |
| A motor with high starting torque must be used. |
23
Medium
What does the thermostatic expansion valve regulate?
| Evaporation pressure after. |
| Cooling. |
| The mass flow of the refrigerant injected into the evaporator. |
| Discharge temperature. |
24
Medium
The refrigerant absorbs heat when...
| freezes. |
| it evaporates. |
| it condenses. |
| sublimates |
25
Medium
In the case of a thermostatic expansion valve, the manufacturer specifies...
| …the degree of refrigerant expansion. |
| ...the superheat value during valve operation. |
| ...the static superheat of the valve. |
| ...the degree to which the valve is filled with refrigerant liquid. |
26
Medium
How do we charge a new or repaired system with refrigerant when it is fitted with an expansion valve
| to the suction side of the compressor. |
| behind the condenser to the liquid refrigerant receiver. |
| Charging with refrigerant takes place during operation via the outlet connection of the refrigerant capillary tube. |
| in any way. |
27
Medium
What does a thermostatic/electronic expansion valve regulate?
| The number of revolutions of the compressor per unit of time. |
| The amount of refrigerant by controlling the evaporator superheat. |
| The evaporation pressure, closing when it falls below the setpoint temperature. |
| Condenser subcooling by adjusting the condensing pressure. |
28
Medium
What does the MOP function in expansion valves mean?
| This means that these expansion valves are set to prevent overheating. |
| This means that these expansion valves are set to a specific suction pressure. |
| This means that these expansion valves are set to limit subcooling. |
| It means that these expansion valves are set to limit the maximum operating pressure. |
29
Medium
The lower the temperature of the liquid refrigerant upstream of the expansion valve,
| ... the higher the theoretical coefficient of cooling capacity qo will be, and the greater the cooling capacity Qo will be. |
| ...the lower the theoretical coefficient of cooling efficiency qo will be, and the lower the system’s energy efficiency will be. |
| ...the lower the theoretical coefficient of cooling efficiency qo will be, whilst the cooling capacity Qo remains unchanged. |
| ...the lower the theoretical coefficient of refrigeration efficiency qo will be, and the lower the refrigeration capacity Qo will be. |
30
Medium
The MOP point in the expansion valve, due to the maximum evaporation temperature of the refrigeration system, ...
| The value of the MOP point is irrelevant. |
| ...must be approximately 7 K higher. |
| ...must be approximately 7 K lower. |
| ...must be approximately 5 K lower. |
31
Medium
What is the function of the suction pressure regulator?
| To maintain the suction pressure at the highest possible level. |
| It limits the suction pressure and protects the compressor from excessively high suction pressure. |
| It prevents a drop in suction pressure and, if necessary, shuts down the refrigeration system. |
| It maintains the suction pressure at a constant level. |
32
Medium
What is the function of the valve regulating water flow through the condenser?
| To maintain the condensing pressure at the lowest possible level. |
| To maintain the condensing pressure at the highest possible level. |
| To maintain the condensing pressure at a constant level. |
| To maintain the water temperature at the highest level. |
33
Medium
The use of a refrigerant distributor requires a thermostatic expansion valve …
| … with external pressure equalisation. |
| … with internal pressure equalisation. |
| … with an adsorption-type sensor filling. |
| … with a MOP function. |
34
Medium
What properties should good insulation materials have?
| It must be able to absorb large amounts of moisture. |
| It must have a high thermal conductivity. |
| It must have a low thermal conductivity. |
| It must have a good antistatic coating |
35
Medium
When do we encounter the superheated state?
| This is the temperature difference between the actual vapour temperature and the vapour temperature at saturation. |
| It is the temperature difference between the evaporation temperature and the ambient temperature. |
| It is a condition in which the compressor motor temperature rises excessively. |
| This is a state that arises as a result of the temperature difference between the suction side and the discharge side of a compressor. |
36
Medium
How can you check whether the liquid refrigerant is reaching the expansion valve without vapour bubbles?
| We check using a liquid pressure gauge. |
| We check this using a sight glass. |
| We check using a pressure gauge fitted on the discharge side of the compressor. |
| We are unable to check this. |
37
Medium
The liquid lines are located...
| between the evaporator and the compressor. |
| between the compressor and the condenser. |
| between the evaporator and the regenerative heat exchanger. |
| between the condenser and the liquid receiver. |
38
Medium
What is the function of the liquid receiver in a refrigeration system?
| When an installation technician does not know the exact amount of refrigerant required, the tank serves as a safety reserve for the entire refrigeration system. |
| The reservoir is used to further cool the liquefied refrigerant leaving the condenser. |
| The tank is used to store and ensure an adequate supply of refrigerant in the event of fluctuations in the thermal load of the refrigeration system. |
| The tank is used to collect the liquid refrigerant and excess oil in the system. |
39
Medium
What is the purpose of the liquid refrigerant reservoir?
| The tank is required during maintenance work, when there is a temporary need to store the refrigerant that has been circulating in the refrigeration system up to that point. |
| The tank is used to collect the liquid refrigerant and excess oil in the system. |
| The tank is used to further cool the liquefied refrigerant leaving the condenser. |
| When an installation technician does not know the exact amount of refrigerant required, the tank serves as a safety reserve for the entire refrigeration system. |
40
Medium
Where should the liquid receiver be installed?
| It should be fitted just before the compressor. |
| It should be installed downstream of the condenser, upstream of the expansion valve. |
| It should be fitted after the evaporator. |
| It should be fitted between the compressor and the condenser. |
41
Medium
What is the function of the suction pressure regulator fitted to the suction pipe when the compressor starts up?
| It regulates the evaporation pressure. |
| It closes when the suction pressure upstream of the compressor drops. |
| It opens when the suction pressure upstream of the compressor drops. |
| It regulates the condensing pressure. |
42
Medium
The use of microchannel heat exchangers, compared with conventional heat exchangers made of copper tubes and fins, results in:
| An increase in the amount of refrigerant in the system and an increase in condensing pressure. |
| A reduction in the amount of refrigerant and an increase in energy efficiency. |
| A reduction in the system’s energy efficiency. |
| There is no effect whatsoever on either the amount of refrigerant or energy efficiency. |
43
Medium
Which refrigerants belong to the HFC group?
| R134a, R404A, R507A, R410A. |
| R134a, R32, R22, R507A, R290. |
| R22, R401A. |
| R11, R12, R502. |
44
Medium
Which refrigerants belong to the HFO group?
| R134a, R290. |
| R22, R12. |
| R134a, R404A. |
| R1234yf, R1234ze. |
45
Medium
What are the characteristics of R410A refrigerant compared to R407C refrigerant?
| The saturation pressure of R407C refrigerant is much higher than that of R410A. |
| The saturation pressure of both refrigerants is roughly the same. |
| The saturation pressure of R410A refrigerant is higher than that of R407C. |
| The saturation pressure of R407C is 150% higher than that of R410A. |
46
Medium
What does the TEWI parameter define?
| This is a parameter that quantifies the impact of refrigerants on the ozone layer. |
| This is a parameter defining the ozone layer’s ability to recover (regenerate). |
| It is the total (global) greenhouse gas equivalent – this indicator takes into account the refrigerant’s direct capacity to contribute to the greenhouse effect and its indirect impact on it through the energy consumption (during the production of which CO₂ is generated) by the refrigeration unit in operation. |
| It is the global warming potential, expressed in terms of carbon dioxide (CO₂), over a 100-year time horizon. |
47
Medium
What are the characteristics of R452A refrigerant compared to R404A?
| The temperature glide of R452A is half that of R404A. |
| It is a non-flammable refrigerant, a mixture from the HFC/HFO group with thermodynamic properties similar to those of R404A and a GWP approximately 45% lower than that of R404A. |
| It is a flammable and toxic homogeneous refrigerant from the HFC group. |
| Both refrigerants are homogeneous refrigerants with no temperature glide. |
48
Medium
What is the distinguishing feature of R1234yf compared to R134a?
| A higher critical temperature. |
| a higher boiling point at standard pressure. |
| greater toxicity. |
| greater flammability. |
49
Medium
Compared to R134a, the refrigerant CO₂ is characterised by?
| It has a temperature slip of 7K greater than R134a. |
| It has identical thermodynamic properties and can be used as a drop-in replacement for R134a. |
| Unlike R134a, it is an azeotropic mixture. |
| It has a lower critical temperature, higher operating pressures and greater volumetric efficiency, allowing for the use of a smaller quantity of refrigerant compared to R134a. |
50
Medium
The following are not classified as fluorinated greenhouse gases:
| Sulphur hexafluoride (SF6). |
| Carbon dioxide (CO₂). |
| Hydrofluorocarbons (HFCs). |
| Perfluorocarbons (PFCs). |
51
Difficult
What additional protective equipment will you use when soldering systems containing HC refrigerants?
| Tinted safety goggles |
| Fire blanket |
| Flammable gas detector |
| High-visibility jacket |
52
Difficult
Why can’t a sealed high-pressure switch be replaced with a standard mechanical one in a system containing a flammable refrigerant?
| Dust and moisture may enter |
| There is a risk of refrigerant leakage |
| The pressure switch setting will not be correct |
| It is a potential source of ignition |
53
Difficult
What is the minimum distance from the work area where HC refrigerants are used at which there must be no sources of ignition?
| 3 m |
| 1 m |
| 0.5 m |
| 2 m |
54
Difficult
What is the maximum safe charge for a recovery cylinder with R32 refrigerant, if it can be charged with 20 kg of R410A?
| 20 kg |
| 18 kg |
| 33 kg |
| 9 kg |
55
Difficult
According to EN 378, what is the maximum charge of an A3 refrigerant for a display unit (hermetic, with an internal condenser) located in the ground-floor retail area of a supermarket?
| 1.5 kg |
| 10 kg |
| 2.5 kg |
| 1.0 kg |
56
Difficult
How can a vacuum pump be used safely to evacuate a system containing a flammable refrigerant?
| Position the vacuum pump 3 metres above floor level |
| Fit a long hose to the pump outlet to remove HC away from the system |
| There is no need to evacuate such systems |
| Use an ATEX-certified vacuum pump in a well-ventilated area |
57
Medium
What is the greenhouse effect?
| It alters the composition of the atmospheric air. |
| It causes an increase in temperature close to the Earth’s surface (up to 10 metres above the surface). |
| It lowers the average surface temperature of the Earth. |
| It causes the thermal radiation emitted by the Earth to be trapped in the upper atmosphere. |
58
Difficult
What protective equipment must you have in your car when transporting flammable substances?
| A fire extinguisher |
| Fire blanket |
| Tinted safety goggles |
| Thick gloves |
59
Difficult
How would you remove the refrigerant from a 10kg R32 water chiller, located outdoors, before unsoldering the connections?
| Vent the R32 to the outside; charge the system with nitrogen until an overpressure is achieved, vent and drain the system twice, charge the system with nitrogen a third time and vent |
| Vent the R32 to the outside and drain the system |
| Recover the R32 until a vacuum is achieved |
| Recover the R32 until a vacuum is achieved, then charge the system with nitrogen to a relative pressure of 0.1 bar g |
60
Medium
What is R1270?
| Isobutane |
| Butane |
| Propylen |
| Propene |
61
Difficult
Which of the following leak detection methods cannot be used to locate an HC refrigerant leak?
| Leak detection foam |
| Soapy water solution |
| Electronic HFC leak detector |
| Electronic leak detector for flammable refrigerants |
62
Difficult
What is the most important difference between a flammable refrigerant recovery unit and a standard one?
| A different colour for the station |
| A flammable refrigerant recovery unit has no ignition sources |
| Different connection sizes |
| Different low-pressure switch setting |
63
Difficult
Which of the following is a source of ignition?
| Contactor |
| Defrost heating element |
| ‘n’ type thermostat |
| Ex-certified evaporator fan motor |
64
Difficult
What substance is produced when R32 is burnt?
| Carbon monoxide |
| Hydrochloric acid |
| Hydrogen fluoride |
| Phosgene |
65
Difficult
What type of refrigerant is R1234ze?
| Hydrofluoroolefin |
| Hydrocarbon |
| Hydrochlorofluoro-hydrocarbon |
| Chloro-fluoro-hydrocarbon |
66
Difficult
What hazards does a Group A3 refrigerant pose?
| High toxicity, moderate flammability |
| High toxicity, high flammability |
| Low toxicity, moderate flammability |
| Low toxicity, highly flammable |
67
Difficult
According to EN 378, what is the maximum charge of R290 in a cold store measuring 5 m x 3 m x 2.5 m in height (the LFL for R290 is 0.038 kg/m³)?
| 1.5 kg |
| 0.285 kg |
| 1.0 kg |
| 4.93 kg |
68
Easy
What does the GWP indicator mean?
| This is an indicator expressing the potential to deplete the ozone layer. |
| It is a unit expressing the ability to enhance the ozone layer. |
| It is an expansion of the abbreviation ‘Global Warming Potential’ and indicates the rate of increase in air temperature |
| It is the global warming potential. The impact on global warming caused by 1 kg of a given gas or chemical substance, expressed as a GWP value, where GWP=1 represents the global warming caused by 1 kg of CO₂ over a period of 100 years (the global warming potential of a unit mass of a given gas over a 100-year period, relative to the warming caused by a unit mass of CO₂). |
69
Difficult
What is the cooling capacity of R32 compared to R410A?
| 60% |
| 75% |
| 130% |
| 105% |
70
Difficult
Why are Ex-certified evaporator fan motors used in some systems with flammable refrigerants?
| Because they must be kept running continuously to disperse the leaking refrigerant |
| Because they are more energy-efficient |
| Because they are more reliable |
| To avoid a source of ignition in the event of a flammable refrigerant leak |
71
Difficult
Why is the difference in density between HC and HFC refrigerants important?
| Because it affects the charge weight |
| Because it affects energy efficiency |
| Because it affects the charging rate |
| Because it increases operating pressures |
72
Difficult
What is the GWP value for R290?
| A. 0.02 |
| 3 |
| 675 |
| 7 |
73
Difficult
Which of the following is not a source of ignition?
| Light switch |
| An Ex-certified fan motor |
| Open mechanical pressure switch |
| Electrical switch |
74
Difficult
What is R290?
| Ethane |
| Butane |
| Propene |
| Propylene |
75
Difficult
According to EN 378, what is the maximum HC refrigerant charge for a display unit (hermetic system with an internal condenser) located in the ground-floor shopping area of a supermarket?
| 2.5 kg |
| 1.5 kg |
| 150 g |
| 1.0 kg |
76
Difficult
Why can’t a standard relay be fitted when retrofitting a compressor’s electrical system for flammable refrigerants?
| A relay is never required for compressors using flammable refrigerants |
| It could be a source of ignition |
| Current consumption differs for compressors using flammable refrigerants compared to those using HFCs |
| The method of starting the compressor motor differs from that used with HFCs |
77
Difficult
What is the minimum distance from the work area where HC refrigerants are used at which there must be no sources of ignition?
| 10 m |
| 5 m |
| 1 m |
| 3 m |
78
Difficult
What is the safe charge for a recovery cylinder with R290 refrigerant, if it can be charged with 10 kg of R404A?
| 20 kg |
| 17 kg |
| 8 kg |
| 3.6 kg |
79
Medium
How do refrigeration systems contribute to the greenhouse effect, i.e. the rise in atmospheric temperature at the Earth’s surface?
| Indirectly (through energy consumption) and directly (through the emission of refrigerants into the atmosphere) |
| Refrigeration equipment emits CO₂ both directly and indirectly. |
| As a result of oil being emitted into the atmosphere by the condenser and filter |
| Through the leakage of refrigerant into the environment. |
80
Difficult
How can a vacuum pump be used safely to evacuate a system containing R290?
| Use an ATEX-certified vacuum pump in a well-ventilated area |
| Position the vacuum pump 3 metres above floor level |
| There is no need to evacuate systems containing R290 |
| Fit a long hose to the pump outlet to remove HC away from the system |
81
Difficult
In accordance with ADR regulations, what protective equipment must you have in your vehicle when transporting flammable refrigerants?
| A fire extinguisher |
| Thick gloves |
| Tinted safety goggles |
| Fire blanket |
82
Difficult
How do you ensure it is safe to light the torch needed to desolder joints in a system that has been evacuated of flammable refrigerant?
| Work outdoors |
| Purge the system with oxygen-free nitrogen |
| Ensure the area is well ventilated and use a flammable gas detector to check the area |
| You must not desolder joints on a system containing a flammable refrigerant; they must be cut using a pipe cutter |
83
Difficult
How would you remove the refrigerant from a system containing 100 g of R1270 so that it is ready for the joints to be desoldered?
| Vent the R1270 to the outside; charge the system with nitrogen until an overpressure is reached, vent and evacuate the system twice, charge the system with nitrogen a third time and vent |
| Recover the R1270 until a vacuum is achieved |
| Vent the R1270 to the outside and drain the system |
| Recover the R1270 until a vacuum is achieved, then charge the system with nitrogen to a relative pressure of 0.1 bar g |
84
Difficult
Which of the following leak detection methods cannot be used to locate a leak of R290 refrigerant?
| Electronic HFC leak detector |
| Fluorescent dye and a UV lamp |
| Electronic leak detector for flammable refrigerants |
| Leak detection foam |
85
Difficult
Why can’t recovery stations designed for HFCs be used with R600a?
| The oil in the recovery unit is not soluble in R600a |
| The recovery unit cannot withstand the working pressure of R600a |
| It contains ignition sources |
| The low-pressure switch setting will not be suitable for R600a due to its lower operating pressure |
86
Difficult
According to EN 378, what is the maximum charge of R1234ze in a cold store measuring 5 m x 3 m x 2.5 m in height (the LFL for R1234ze is 0.303 kg/m³)?
| 6.18 kg |
| 227 kg |
| 618 kg |
| 2.27 kg |
87
Difficult
What type of refrigerant is R32?
| Carbon dioxide |
| Hydrocarbon |
| Hydrofluorocarbon |
| Hydrofluoroolefin |
88
Difficult
What hazards do A2L refrigerants pose?
| Low toxicity, moderate flammability |
| High toxicity, moderate flammability |
| Low toxicity, high flammability |
| High toxicity, high flammability |
89
Difficult
What danger is associated with the combustion of HFO or HFC refrigerants?
| Citric acid is produced |
| Hydrogen fluoride is produced |
| Phosgene is produced |
| Nitrous oxide is produced |
90
Medium
What is the greenhouse effect, also known as the greenhouse phenomenon?
| It is the phenomenon of heat being trapped in the Earth’s atmosphere (making it difficult for heat to radiate out of the Earth’s atmosphere). |
| The absorption of radiation reaching the Earth’s surface. |
| This is the formation of a layer that traps only the heat generated by the combustion of fuel in aeroplanes. |
| The filtering out of solar radiation. |
91
Difficult
What is the approximate displacement volume required for a compressor running on R600a compared to one running on R134a to achieve the same cooling capacity?
| Half |
| Seven times |
| The same |
| Twice |
92
Difficult
What is the GWP value for R32?
| 675 |
| 7 |
| 3 |
| 0 |
93
Difficult
Why is the accuracy of the charge weight more important for systems critically charged with R290 compared to those using HFCs
| Because R290 is only used in systems with a charge of less than 150g |
| Due to lower operating pressures |
| Because these systems never have liquid receivers |
| The charge mass is significantly lower than in an HFC system, as the density is much lower |
94
Difficult
Why does the condenser fan run continuously in some systems using R1270?
| To reduce energy consumption |
| To ensure that the discharge pressure never becomes excessive |
| To dilute the refrigerant in the event of a leak |
| To prevent the build-up of contaminants in the condenser |
95
Medium
Which EU regulation is currently the primary piece of legislation governing the use of fluorinated greenhouse gases (F-gases) in the European Union?
| Directive 2009/125/EC |
| Regulation (EU) No 517/2014 |
| Regulation (EU) 2024/573 |
| Regulation (EU) 2015/1188 |
96
Medium
What is the main objective of Regulation (EU) 2024/573?
| Standardising metal recycling standards |
| Prevention of F-gas emissions and the achievement of the EU’s climate targets |
| To reduce taxes on refrigeration equipment |
| To facilitate the import of electrical appliances |
97
Medium
What are the obligations of manufacturers of refrigeration appliances in the context of ecodesign, and which regulation governs them?
| Manufacturers must comply solely with ISO 9001 standards, without any link to EU regulations |
| The manufacturer must ensure minimum energy efficiency, reparability and recyclability of equipment, as regulated by Regulation (EU) 2019/2019 |
| Manufacturers are only required to use energy labels, and this is regulated by Regulation (EU) 2024/573 |
| Manufacturers are only required to declare the quantity of F-gas used, in accordance with Regulation (EU) No 517/2014 |
98
Medium
What is the main objective of the Ecodesign Directive?
| To facilitate the import of products from outside the EU |
| To standardise the appearance of products in the EU |
| Reducing the negative environmental impact of products by improving energy efficiency, durability and recyclability |
| To increase sales of electrical appliances in the EU |
99
Medium
What is the function of a ball valve in a refrigeration system?
| It regulates the temperature of the refrigerant |
| Enables the refrigerant flow to be completely shut off |
| It measures the moisture content of the refrigerant |
| It prevents excessive pressure build-up in the system |
100
Easy
What is the main function of a relief valve?
| Prevents the evaporator from freezing |
| It controls the oil level in the compressor |
| It monitors the moisture content of the refrigerant |
| Relieves pressure in the system in the event of excessive pressure |
101
Medium
How do certain substances or gases contribute to the greenhouse effect?
| When released into the atmosphere, certain substances cause the air to heat up as a result of reactions with the oxygen and nitrogen contained in the air. |
| Certain substances trap the thermal radiation that the Earth should radiate into the atmosphere. In this way, the Earth gradually warms up and the greenhouse effect occurs. |
| Some substances damage the ozone layer |
| Certain substances limit the impact of the Sun’s ultraviolet radiation on the Earth’s surface. |
102
Medium
What is the purpose of the sight glass in a refrigeration system?
| To shut off the flow in the event of an emergency |
| To measure the condenser temperature |
| To regulate compressor pressure |
| For visual assessment of the presence of refrigerant and oil, and for monitoring moisture levels |
103
Medium
What is the function of the temperature regulator in a refrigeration system?
| Controls the operation of the compressor and valves to maintain the set temperature |
| It restricts oil flow |
| To maintain a constant pressure in the compressor |
| It drains excess refrigerant into the receiver |
104
Difficult
What is the role of the liquid separator in systems using flammable or toxic refrigerants?
| They are used solely to measure the moisture content of the refrigerant |
| It separates the liquid from the oil |
| Heats the refrigerant before it enters the evaporator |
| It prevents liquid from entering the compressor |
105
Difficult
What is the function of an oil separator in systems using flammable or toxic refrigerants?
| They are used solely to measure the moisture content of the refrigerant |
| Separates oil from the refrigerant and facilitates the return of oil to the compressor |
| Heats the refrigerant before it enters the evaporator |
| It prevents liquid from entering the compressor |
106
Medium
What is the purpose of oil level regulators in a refrigeration system?
| They drain off excess refrigerant |
| Maintains the correct oil level in the compressor |
| They control the pressure in the condenser |
| They control the evaporator temperature |
107
Medium
What is the function of the refrigerant receiver in the system?
| Regulates the oil flow |
| Stores excess refrigerant and facilitates the detection of leaks |
| It controls the evaporator temperature |
| It maintains a constant pressure in the system |
108
Medium
What is the role of the manifold thermometer in the refrigeration system?
| Relieves pressure in the system in the event of excessive pressure |
| Measures the refrigerant temperature at the compressor inlet and outlet, which helps to identify leaks |
| Controls the oil level |
| It monitors the moisture content of the refrigerant |
109
Medium
What is the role of the defrost control valves?
| They control the pressure in the compressor |
| They are used to monitor the moisture content of the refrigerant |
| They drain off excess oil |
| Protect the evaporator from excessive icing and reduce the risk of leaks |
110
Difficult
Why do CO₂ refrigeration systems require special attention when separating liquid and oil?
| CO₂ is flammable, so separators cannot be used |
| CO₂ cannot be used in systems with sight glasses |
| CO₂ does not require lubrication, so separators are unnecessary |
| CO₂ operates at high pressure, which increases the risk of compressor failure and leaks |
111
Difficult
What is the critical pressure of CO₂ (R744)?
| Approximately 120 bar |
| Approximately 31 bar |
| Approximately 74 bar |
| Approximately 10 bar |
112
Easy
What is the base unit of pressure according to the International System of Units (SI)?
| Psi |
| Atm. |
| bar |
| Pa |
113
Medium
Where can I find lists detailing fluorinated greenhouse gases (F-gases)?
| In the Vienna Convention for the Protection of the Ozone Layer. |
| In the Regulation of the Minister for the Economy on the introduction of a list of fluorinated greenhouse gases. |
| In the Act on Ozone-Depleting Substances and Certain Fluorinated Greenhouse Gases. |
| In Regulation (EU) No 2024/573 of the European Parliament and of the Council |
114
Difficult
What characterises the transcritical process in CO₂ systems?
| It is irrelevant to the operation of the system |
| It occurs only at low temperatures |
| Conventional condensation occurs |
| The system operates above the critical point and the refrigerant does not condense in the conventional manner |
115
Difficult
What characterises the subcritical CO₂ process?
| The conventional condensation process below the critical point |
| The absence of condensation |
| Operation above the critical point |
| The absence of evaporation |
116
Difficult
What is the log(p)-h diagram for CO₂ used for?
| To measure temperature |
| For analysing thermodynamic processes in a refrigeration system |
| To regulate pressure |
| To detect leaks |
117
Difficult
What can be read from the log(p)-h graph?
| Pressure, enthalpy, temperature and state of the refrigerant |
| Only the humidity |
| Only the amount of refrigerant |
| Only the temperature |
118
Difficult
What are CO₂ saturation tables used for?
| To determine the oil quantity |
| To determine the relationship between temperature and pressure at saturation |
| To regulate the compressor |
| To measure humidity |
119
Difficult
What does the CO₂ saturation state mean?
| A state of high pressure |
| Dry ice state |
| Equilibrium between the liquid and vapour phases |
| A state in which the refrigerant is only a gas |
120
Difficult
When can dry ice (solid CO₂) form?
| In the event of a sudden drop in pressure and temperature below the triple point |
| During normal operation of the system |
| At high pressure |
| At high temperature |
121
Difficult
What risks are associated with the formation of dry ice in a CO₂ system?
| No risk |
| Improved efficiency |
| Pressure reduction |
| Blocked pipes and system damage |
122
Difficult
How does the CO₂ pressure change as the temperature rises?
| It decreases |
| Rises sharply |
| It remains the same |
| It first decreases, then increases |
123
Difficult
Why is understanding the log(p)-h graph particularly important for CO₂?
| It is only used for design purposes |
| It only applies to NH₃ |
| It doesn’t matter |
| As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis |
124
Medium
Where can I find the lists specifying controlled substances?
| In Regulation (EU) No 2024/590 of the European Parliament and of the Council. |
| In the Regulation of the Minister for the Environment on the list of controlled substances. |
| In the Vienna Convention for the Protection of the Ozone Layer. |
| In the current Act on Ozone-Depleting Substances and Certain Fluorinated Greenhouse Gases. |
125
Difficult
What happens to CO₂ above the critical point?
| It transitions to a supercritical state (no distinction between liquid and gas) |
| It ceases to conduct heat |
| It turns into a solid |
| It turns into a liquid |
126
Difficult
Why do CO₂ systems require precise pressure control?
| Due to low pressures |
| Due to significant pressure changes with temperature fluctuations |
| Because there are no valves |
| They do not require control |
127
Medium
Why is ammonia (NH₃) considered a toxic refrigerant?
| It does not react with water, which makes it difficult to neutralise |
| It is highly irritating to the respiratory tract and toxic if inhaled |
| It is flammable and can form explosive mixtures with air |
| It is colourless and odourless, so it is difficult to detect |
128
Difficult
What is the main difference between a dry evaporator and a flooded evaporator?
| A dry evaporator allows the entire refrigerant to evaporate in the pipe upstream of the compressor; in a flooded evaporator, part of the refrigerant remains in a liquid state within the evaporator |
| A dry evaporator does not require an expansion valve, whereas a flooded one does |
| A dry evaporator is filled with refrigerant liquid, whilst a flooded evaporator is filled with gas |
| A dry evaporator has a lower operating pressure than a flooded one |
129
Difficult
What is the typical pressure in deep-freezing systems (below −40 °C) for an evaporator in a system using R717?
| Atmospheric pressure, approximately 1 bar |
| Negative pressure (vacuum), below 0 bar |
| A pressure varying between 10 and 20 bar |
| Positive pressure, in the range of 5–10 bar |
130
Difficult
Why are PFAS substances formed as a result of the decomposition of certain F-gases problematic?
| They are persistent, accumulate in the environment and may be toxic |
| They are climate-neutral |
| They cause rapid cooling of the atmosphere |
| They are readily biodegradable, so they only pollute the environment for a short time |
131
Difficult
What is the basic requirement when charging a system with R717 (NH₃)?
| NH₃ can be charged together with air |
| Charging must only take place at temperatures below 0°C |
| Charging can be carried out without personal protective equipment |
| Charging should take place in a well-ventilated area using appropriate personal protective equipment |
132
Difficult
How should oil be handled in systems using R717?
| The oil does not require any monitoring |
| Oil has no effect on the system’s operation |
| The oil should be checked regularly and any excess removed from the lower parts of the units to prevent reduced heat transfer and leaks |
| Oil can be mixed with any refrigerant |
133
Difficult
What is the correct procedure for recovering R717 from a system?
| Recovery is not required |
| The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃ |
| The gas can be released into the atmosphere |
| The refrigerant can be drained into the sewer system |
134
Difficult
How should R717 (NH₃) be stored?
| Near heat sources |
| In any open containers |
| In sealed, labelled containers, in a cool and well-ventilated place |
| In unmarked plastic containers |
135
Medium
Where and by when should annual reports on ODS and F-gases be submitted?
| Reports for the previous year must be submitted by 31 March of the relevant year electronically to the Ministry of the Environment. |
| Reports on ODS and F-gases for the previous year must be submitted by 28 February of the following year, via the IT system available in the reports database at the Office for the Protection of the Ozone Layer and Climate (BOWOiK) on the ICHP website. |
| Reports for the previous year must be submitted by 31 January electronically by completing the special forms available in the central register of operators ‘CRO’. |
| Reports must be submitted by the end of the relevant calendar year, using a special form at the regional branch of the Office of Technical Inspection (UDT) |
136
Difficult
What should be done in the event of R717 contamination?
| Add water to dilute it |
| The refrigerant must be purified or sent for disposal in accordance with regulations |
| Release into the atmosphere |
| Continue to use without restriction |
137
Difficult
What is the main hazard associated with an R717 leak during maintenance work?
| Toxic to humans and may cause chemical burns |
| No risk whatsoever |
| Increased cooling efficiency |
| Damage to electrical equipment only |
138
Difficult
What action should be taken if an NH₃ leak is detected?
| Close your eyes and carry on working |
| Increase the pressure in the system |
| Ignore it and carry on working |
| Evacuate personnel immediately and remove the source of the leak, if it is safe to do so |
139
Difficult
What role do scrubbers play in NH₃ systems?
| Neutralises ammonia through absorption in a liquid (e.g. water) |
| They store the refrigerant |
| They are used to measure temperature |
| They increase the pressure in the system |
140
Difficult
How should the system be prepared before filling with R717?
| The pressure must be increased above the standard level |
| Simply start it up |
| Check for leaks, remove air and moisture, and create a vacuum |
| There is no need to check it |
141
Difficult
What are the transport requirements for R717?
| Transport is not subject to regulations |
| Must be transported in suitable, labelled containers in accordance with ADR regulations |
| It can be transported without labelling |
| It can be transported in open containers |
142
Difficult
What personal protective equipment is required when working with NH₃?
| Only a safety helmet |
| Workwear only |
| No requirements |
| Safety goggles, gloves and respiratory protective equipment |
143
Medium
Which measure has the greatest impact on improving the compressor’s energy efficiency during installation?
| Increasing the amount of refrigerant |
| Installation without a leak test |
| Correctly create a vacuum and remove moisture from the system |
| Installation without filters |
144
Medium
How does regular monitoring of the oil level affect the compressor’s operation?
| Causes a rise in pressure |
| Ensures proper lubrication and improves energy efficiency |
| It reduces cooling capacity |
| It has no effect |
145
Medium
How do system leaks affect the compressor’s energy efficiency?
| These cause a drop in performance and an increase in energy consumption |
| They lower the operating temperature |
| Have no effect |
| They improve efficiency |
146
Medium
Regulation (EC) No 2024/590 relates to:
| Alternative refrigerants serving as substitutes for fluorinated greenhouse gases. |
| Ozone-depleting substances. |
| Health and safety at work during the recovery of refrigerants. |
| The conditions for obtaining F-gas certificates by companies carrying out the recovery and reclamation of waste refrigerants. |
147
Medium
What is the significance of regulating suction and discharge pressure?
| Increases oil consumption |
| Causes leaks |
| It has no effect on efficiency |
| Helps maintain optimal operating conditions for the compressor |
148
Medium
What maintenance measure reduces the compressor’s energy consumption?
| Regular replacement of filters and dryers |
| Disabling safety devices |
| Lack of servicing |
| Increasing the refrigerant charge |
149
Medium
How does the presence of air in the refrigeration system affect performance?
| Leads to increased pressure and reduced efficiency |
| It has no effect |
| Reduces energy consumption |
| It improves efficiency |
150
Medium
What role do control systems (e.g. regulators) play in compressor efficiency?
| It doesn’t matter |
| Enables optimisation of operation and a reduction in energy consumption |
| It increases the amount of refrigerant |
| Causes leaks |
151
Medium
How does refrigerant superheat at the compressor suction affect performance?
| Excessive overheating reduces efficiency and increases energy consumption |
| It only causes a drop in temperature |
| It always improves performance |
| It has no effect |
152
Medium
How does the correct layout of the system affect efficiency?
| It doesn’t matter |
| It increases the pressure |
| Shortens flow paths and reduces energy losses |
| It causes the temperature to rise |
153
Medium
How important is pipe insulation?
| It increases energy consumption |
| It has no effect |
| Causes a rise in pressure |
| Reduces heat loss and improves energy efficiency |
154
Medium
Which measure most improves the condenser’s energy efficiency?
| Restricted airflow |
| Regular cleaning of heat exchange surfaces |
| Contamination of the heat exchange surface |
| Increasing the amount of refrigerant |
155
Medium
How does a dirty condenser affect the operation of the refrigeration system?
| Causes an increase in pressure and energy consumption by the compressor |
| It improves efficiency |
| It has no effect |
| It lowers the condensing pressure |
156
Medium
Why is adequate airflow through an air-cooled condenser important?
| Causes a drop in pressure |
| It doesn’t matter |
| Ensures effective heat dissipation and improves energy efficiency |
| Insufficient airflow reduces efficiency |
157
Medium
Which refrigerants cause damage to the ozone layer?
| All refrigerants that contain chlorine or bromine in their molecules. |
| All refrigerants that contain fluorine and hydrogen in their molecules. |
| All refrigerants that contain carbon in their molecular structure. |
| All refrigerants that are hydrocarbon derivatives. |
158
Medium
How does the presence of limescale in a water-cooled condenser affect performance?
| It lowers the condensation temperature |
| It has no effect |
| Impairs heat exchange and increases energy consumption |
| It improves heat transfer |
159
Medium
How does correct condensation pressure control affect efficiency?
| Maintains optimum operating conditions and reduces energy consumption |
| Causes leaks |
| It increases energy consumption |
| It has no effect |
160
Medium
How do condenser leaks affect energy efficiency?
| Have no effect |
| They lower the temperature |
| They improve efficiency |
| Causes refrigerant loss and a drop in efficiency |
161
Medium
How important is the correct positioning of an air-cooled condenser?
| It should be installed in a well-ventilated area with unobstructed airflow |
| It doesn’t matter |
| It should be close to heat sources |
| It should be housed in a small room |
162
Medium
How does hot air recirculation affect the condenser?
| Impairs cooling and increases energy consumption |
| It improves efficiency |
| It has no effect |
| It reduces the pressure |
163
Medium
How does the insulation of central heating and domestic hot water pipework affect the operation of the heat pump’s condenser?
| It impairs cooling |
| It increases the pressure |
| Reduces energy losses and improves the efficiency of the entire system |
| It doesn’t matter |
164
Medium
Which measure most improves the energy efficiency of the evaporator?
| Increasing the condensation temperature |
| Regular defrosting of the evaporator |
| Restricted airflow |
| Increasing the amount of refrigerant |
165
Medium
How does evaporator icing affect the system’s operation?
| Impairs heat exchange and increases energy consumption |
| It lowers the condensation temperature |
| It has no effect |
| It improves cooling performance |
166
Medium
How does dirt on the evaporator surface affect its performance?
| It reduces the pressure |
| It improves efficiency |
| Impairs heat exchange and increases energy consumption |
| It has no effect |
167
Medium
What maintenance task is crucial for the evaporator?
| Regular cleaning and defrosting |
| Increasing the refrigerant charge |
| Reduced airflow |
| Lack of maintenance |
168
Medium
What does an F-gas personal certificate (Category A2) authorise?
| for the purchase of lubricants and refrigeration oils, and for the testing of safety valves. |
| to repair, maintain or service refrigeration equipment and systems containing controlled substances. |
| to make permanent joints by brazing in systems containing fluorinated greenhouse gases. |
| To recover refrigerant from equipment containing less than 3 kg of fluorinated greenhouse gases, or less than 6 kg in the case of hermetically sealed systems. |
169
Medium
How does superheating of the refrigerant at the evaporator outlet affect efficiency?
| It only causes a drop in temperature |
| Excessive superheat reduces energy efficiency |
| It always improves performance |
| It has no effect |
170
Medium
How do leaks in the evaporator affect efficiency?
| These cause refrigerant loss and a drop in efficiency |
| Have no effect |
| Improves performance |
| Increase capacity |
171
Medium
How important is correct expansion valve adjustment?
| It doesn’t matter |
| Ensures optimal evaporator charge and improves efficiency |
| It increases energy consumption |
| Causes leaks |
172
Medium
How does inadequate insulation of the heat transfer circuit pipes affect evaporator performance?
| Causes cooling losses and increased energy consumption |
| It improves efficiency |
| It has no effect |
| It lowers the condensation temperature |
173
Medium
How does correct TEV valve adjustment affect the system’s energy efficiency?
| Causes leaks |
| Ensures optimum superheat and improves system efficiency |
| It has no effect |
| It increases energy consumption |
174
Medium
What happens if the superheat set by the TEV is too high?
| It has no effect |
| Cooling efficiency will improve |
| Efficiency will drop because the evaporator is not being fully utilised |
| The refrigerant charge will increase |
175
Medium
How does a low superheat setting on the TEV affect performance?
| It reduces refrigerant flow |
| It may lead to improved efficiency, but it increases the risk of the compressor becoming flooded with liquid |
| It has no effect |
| It increases operational safety |
176
Medium
How do contaminants in the system affect the operation of the TEV?
| They can cause it to become blocked and reduce efficiency |
| Have no effect |
| They improve its performance |
| They lower the temperature |
177
Medium
What role does the filter-drier play in terms of system efficiency?
| It doesn’t matter |
| It lowers the temperature |
| It increases the amount of refrigerant |
| Removes moisture and contaminants, improving the system’s efficiency |
178
Medium
How does proper insulation of components (e.g. pipes near the TEV) affect the system?
| It increases energy consumption |
| It causes leaks |
| It doesn’t matter |
| Prevents unwanted heat gains and improves efficiency |
179
Medium
What does Regulation (EU) No 2024/573 of the European Parliament and of the Council cover?
| The Regulation sets out health and safety requirements for soldering work. |
| The Regulation concerns gases that contribute to the greenhouse effect. |
| The Regulation concerns leak testing of stationary refrigeration, air-conditioning and heat pump equipment containing fluorinated greenhouse gases. The Regulation sets out the requirements relating to leak testing of such equipment. |
| The Regulation sets out requirements relating to brazing of refrigeration systems. |
180
Medium
How important is it to check the operation of the condensing pressure control valve in the system?
| It has no effect |
| It increases energy consumption |
| It causes a significant rise in temperature |
| Ensures operation within the optimum pressure range and reduces energy losses |
181
Medium
How does the correct selection of a TEV affect energy efficiency?
| Ensures the system is matched to its capacity and operates optimally |
| It lowers the temperature |
| It increases the amount of refrigerant |
| It doesn’t matter |
182
Medium
What is the main design difference in hydrocarbon-based refrigeration systems?
| The need for explosion-proof measures due to the flammability of the refrigerant |
| Higher operating pressures |
| Lower energy efficiency |
| No need for safety measures |
183
Medium
What differences are there in the compressors used in hydrocarbon systems?
| No differences |
| They do not require lubrication |
| They must operate at higher pressures |
| They must be designed to operate with flammable refrigerants (e.g. hermetic compressors) |
184
Difficult
What is the main characteristic of R744 (CO₂) refrigeration systems?
| Very high operating pressures |
| Low operating pressures |
| Low energy efficiency |
| No need for regulation |
185
Difficult
What are the requirements for piping materials in CO₂ systems?
| They may be made of any material |
| They must be able to withstand high pressures (e.g. high-grade steel) |
| They must be made exclusively from plastics |
| It does not matter |
186
Difficult
How does a booster system work in CO₂ installations?
| It reduces the pressure in the evaporator |
| It reduces the amount of refrigerant |
| It is used to store the refrigerant |
| It utilises two stages of compression (low and medium pressure) in a single system |
187
Difficult
What is the function of high-pressure control valves in CO₂ systems?
| They regulate oil flow |
| They lower the evaporator temperature |
| They are used to store the refrigerant |
| They control the pressure on the high-pressure side and optimise system operation |
188
Difficult
Why is pressure optimisation in CO₂ systems crucial?
| It reduces the ambient temperature |
| It enables the system to achieve maximum energy efficiency |
| It doesn’t matter |
| It reduces the amount of refrigerant |
189
Difficult
What role do parallel-operating compressors play in CO₂ systems?
| They increase energy consumption |
| They enable gas recovery from the medium-pressure stage and improve efficiency |
| It does not matter |
| They lower the ambient temperature |
190
Medium
How can one check whether the system has been overcharged with refrigerant?
| The compressor will operate under a lower load and the suction pressure will decrease |
| This cannot be checked with sufficient reliability, as the sight glass is not designed for this purpose. |
| Under normal conditions, there is a marked increase in condensing pressure because an excessive amount of refrigerant accumulates in the condenser, reducing the heat exchange surface area within it. |
| The refrigeration system is overcharged with refrigerant whilst in operation, and even under a very small heat load, frost forms on the suction side of the compressor |
191
Difficult
How does an ejector work in a CO₂ system?
| It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency |
| Stores the refrigerant |
| It lowers the evaporator temperature |
| It increases the amount of refrigerant |
192
Difficult
What is the function of liquid ejectors in CO₂ systems?
| They raise the refrigerant temperature |
| They reduce atmospheric pressure |
| They increase the amount of oil |
| They assist with liquid recovery and improve evaporator feed |
193
Difficult
What are the characteristics of partially flooded systems in CO₂ systems?
| Lack of regulation |
| The absence of liquid in the evaporator |
| Low operating pressure |
| The presence of liquid in the evaporator, which improves heat transfer and efficiency |
194
Difficult
What is the main risk associated with static pressure in CO₂ systems?
| A rise in pressure resulting from the refrigerant heating up whilst at rest |
| Increased efficiency |
| A decrease in refrigerant quantity |
| A drop in temperature |
195
Difficult
How can standstill pressure in CO₂ systems be reduced?
| By using parallel compressors and external cooling systems |
| By increasing the temperature |
| By increasing the refrigerant charge |
| By shutting down the system completely |
196
Difficult
What does ‘stagnation’ of a refrigeration system mean in the context of CO₂?
| A drop in temperature |
| Improved efficiency |
| A lack of refrigerant flow, which can lead to increased pressure and safety risks |
| Normal system operation |
197
Difficult
Why do CO₂ systems require more advanced automation than traditional systems?
| Because there are no valves |
| They do not require automation |
| Due to the need for precise control of pressure and temperature |
| Due to low pressures |
198
Difficult
What must be included on the label of a cylinder containing a flammable refrigerant?
| Net weight only |
| Information about the cylinder owner |
| The name of the refrigerant, the hazard symbol and basic safety information |
| Agent name only |
199
Difficult
Why does the absence of a ‘flammable agent’ label on the system pose a significant hazard?
| It may lead to the incorrect selection of oil |
| It may lead to the use of tools that are a source of ignition |
| It has no significant impact on safety |
| It reduces the system’s efficiency |
200
Difficult
Which set of information on the label of a flammable agent cylinder is crucial from a safety perspective?
| Name of the substance, hazard pictogram, UN number |
| Manufacturer’s name and country of origin |
| Cylinder colour and date of manufacture |
| Gross weight and batch number |
201
Medium
Before charging the refrigeration unit with refrigerant, it is essential to…
| carry out a start-up test. |
| check the compressor’s suction and discharge connections. |
| carry out a leak test. |
| complete the unit’s data sheet. |
202
Difficult
What is the requirement regarding the labelling of an installation containing a flammable substance?
| Colour-coding of pipes is sufficient |
| Labelling is not required for hermetically sealed systems |
| Labelling is required only in technical rooms |
| The labelling must indicate the type of substance and the flammability hazard |
203
Difficult
What are the potential consequences of using unsuitable connections in a system containing a flammable substance?
| Risk of leakage and the formation of an explosive mixture |
| Merely a reduction in efficiency |
| Merely installation difficulties |
| No impact on safety |
204
Difficult
What is the purpose of installing gas detectors in a room with a refrigeration system?
| Early detection of refrigerant leaks and prevention of health risks |
| Monitoring pipe pressure |
| Regulating compressor capacity |
| Measuring the refrigerant temperature |
205
Difficult
How often should gas detection sensors in the service room be checked?
| Only after a leak has occurred |
| Before each start-up of the unit |
| Once every 5 years |
| In accordance with the manufacturer’s instructions and applicable health and safety regulations |
206
Difficult
Where should a gas detector be positioned in accordance with EN 378?
| Only at the entrance to the room |
| On the ceiling if the gas is lighter or heavier than air; near the floor if it is lighter or heavier |
| Anywhere in the room |
| Near the control panel |
207
Difficult
How should an employee respond when a gas alarm is triggered?
| Carry on working until they see a leak |
| Switch off the system and wait for the alarm to stop |
| Reduce the pressure in the system |
| Leave the room immediately and notify their supervisor |
208
Difficult
What safety checks should be carried out when installing a new refrigeration system?
| Only the compressor power |
| The presence of health and safety signage, adequate ventilation and gas detectors |
| Is the air filter new? |
| The colour of pipes and hoses |
209
Difficult
Gas detectors should be installed in rooms where:
| The room is less than 5 m² |
| Any refrigerant is present, regardless of the quantity |
| The amount of refrigerant exceeds a specified permissible threshold |
| Ventilation is natural |
210
Difficult
What is the minimum number of emergency exits in a plant room (refrigeration plant room) and how should they be signposted?
| Exits do not need to be signposted if the room is small |
| At least two exits, but signage is optional |
| One exit, clearly marked in the direction of escape |
| One exit with an information sign about the refrigerant |
211
Difficult
Which measure, when installing a system using a flammable refrigerant, improves its energy efficiency?
| Increasing the refrigerant charge |
| Restriction of ventilation |
| No leak test |
| Thorough leak testing and vacuuming |
212
Medium
What information must appear on the unit’s label?
| The manufacturer’s logo and the weight of the unit. |
| Among other things: information stating that the unit contains a fluorinated greenhouse gas, together with the industrial designation of the gas or its chemical name, the mass of the gas and its CO₂ equivalent |
| Markings regarding the weight and capacity of the pipework, together with the colour code and chemical composition of the paints used to coat the frame and casing. |
| It does not matter what should be included on the device label. |
213
Difficult
How do leaks affect systems using flammable refrigerants?
| They cause refrigerant loss, reduced efficiency and a fire hazard |
| They lower the temperature |
| Have no effect |
| They improve efficiency |
214
Difficult
Why is it important to limit the amount of refrigerant in HC systems?
| It lowers the temperature |
| It has no effect |
| It reduces the risk of explosion and improves the system’s operational safety |
| It increases efficiency |
215
Difficult
Why is the cleanliness of heat exchangers in HC systems important?
| It doesn’t matter |
| Causes leaks |
| It improves heat transfer and reduces energy consumption |
| It increases the pressure |
216
Difficult
What maintenance measures improve the efficiency of a system using a flammable refrigerant?
| Increasing the refrigerant charge |
| Lack of servicing |
| Disabling safety devices |
| Regular checks for leaks and operating parameters |
217
Difficult
How does the correct selection of components affect a system using a flammable refrigerant?
| It increases the amount of refrigerant |
| It lowers the temperature |
| It ensures safe and optimal operation and minimises energy losses |
| It doesn’t matter |
218
Difficult
Why is it important to use the correct service tools in HC systems?
| It ensures operational safety and reduces refrigerant losses |
| It increases energy consumption |
| It doesn’t matter |
| Causes leaks |
219
Difficult
How does pipe insulation affect the efficiency of systems containing HC?
| It increases the pressure |
| It doesn’t matter |
| It reduces energy losses and improves efficiency |
| Causes leaks |
220
Difficult
Which safety class applies to R744?
| A1 |
| A3 |
| B2L |
| A2 |
221
Difficult
In an R744 system operating in supercritical mode, the refrigerant entering the evaporator expansion valve is...
| A supercritical fluid |
| A two-phase mixture at intermediate pressure |
| Saturated vapour at intermediate pressure |
| A subcooled liquid |
222
Difficult
In R744 supercritical systems, the gas cooler outlet valve controls:
| The gas cooler fans |
| The pressure in the gas cooler |
| The outlet temperature of the gas cooler |
| The inlet temperature to the gas cooler |
223
Medium
What is the base unit of temperature according to the International System of Units (Système International d’Unités)?
| °C |
| K |
| °R |
| °F |
224
Medium
Which of the following are the most important pieces of information that should be included in the unit’s data sheet:
| The make and model of the unit, so that the manufacturer can be contacted to obtain the technical information necessary for servicing. |
| The owner, installer and service technician of the unit. |
| Operator details, unit details, type and quantity of refrigerant, information regarding servicing and repairs. |
| Information regarding refrigerant recovery and unit dismantling. |
225
Difficult
Which statement best describes the behaviour of R717 and mineral compressor oil?
| R717 does not mix with compressor oil, so the oil remains in the system on the high-pressure side as a layer above the R717 |
| R717 does not mix with compressor oil, so the oil remains in the system on the low-pressure side as a layer beneath the R717 |
| R717 mixes very well with compressor oil and easily returns to the compressor |
| In an R717 system, a return oil line cannot be used because the oil is too hot |
226
Difficult
What is the main reason for using K65 copper tubing in some R744 systems?
| They have good low-temperature performance |
| They bend easily |
| They come in a wider range of diameters |
| They can withstand higher pressures |
227
Difficult
Which of the following statements is correct regarding the installation of Schrader valves?
| Schrader valves must not be used in R744 systems |
| When brazing the valve body to the system, the core must be removed, then refitted and tightened to the correct torque |
| Hydrocarbons leak through Schrader valves |
| All Schrader valve cores are suitable for all refrigerants |
228
Difficult
Which refrigerant can be detected using phenolphthalein paper?
| R744 |
| R1234ze |
| R717 |
| R1270 |
229
Difficult
How does a refrigerant shortage affect the high-pressure side of the system (without discharge pressure regulation)?
| Discharge pressure will be higher, and the degree of subcooling will be higher |
| The discharge pressure will be lower, and the subcooling will be lower |
| Discharge pressure will be lower, subcooling will be higher |
| Discharge pressure will be higher, and the degree of subcooling will be lower |
230
Difficult
What is the benefit of using helium as a tracer gas in nitrogen during a pressure test?
| It has a higher pressure than pure nitrogen |
| It is non-flammable |
| It has a distinct odour |
| It has smaller molecules and diffuses more easily |
231
Difficult
Why should an R744 system that has been drained be initially charged with the refrigerant in gaseous form?
| To prevent damage to the compressor |
| To prevent the formation of dry ice |
| To prevent the drain valve from opening |
| To ensure that R744 is charged slowly |
232
Difficult
If an R744 system contains moisture because it has not been properly drained, what is the likely consequence?
| Reduced cooling capacity |
| Excessively high discharge pressure |
| The formation of hydrogen fluoride, which will decompose into hydrofluoric acid and damage the compressor |
| The formation of carbonic acid, which will cause damage to the system |
233
Difficult
Which system may require manual oil recovery?
| An R717 system |
| Secondary system using R744 |
| Supercritical ‘booster’ system using R744 |
| R744 cascade system |
234
Difficult
The pressure of R744 at a saturation temperature of 20 °C is approx.
| 56 bar g |
| 14 bar g |
| 25 bar g |
| 90 bar g |
235
Medium
Who is responsible for drawing up the equipment or installation record?
| The operator of the unit or system. |
| The equipment maintenance technician. |
| The person responsible for risk assessment. |
| There is no such obligation. |
236
Difficult
Which refrigerant is lighter than air?
| R1234ze |
| R1270 |
| R717 |
| R744 |
237
Difficult
What hazards are associated with a Class A3 safety agent?
| Lower toxicity, does not propagate flames |
| Slightly flammable, lower toxicity |
| High toxicity, does not propagate flames |
| High flammability, lower toxicity |
238
Difficult
18 What is the GWP of R32 (according to AR4)?
| 6 |
| 675 |
| 3945 |
| 0 |
239
Difficult
What factors are taken into account when determining the maximum charge for comfort air-conditioning/heating applications?
| Practical limit, room volume |
| Lower flammability limit, room volume |
| Practical limit, height of the indoor unit, floor area |
| Lower flammability limit, height of the indoor unit, floor area |
240
Difficult
What compressor displacement is required for R1270, relative to R404A compressors for the medium-temperature range (cold store)?
| Similar |
| 50% |
| 600% |
| 150% |
241
Difficult
At an ambient temperature of 25°C, the standby pressure in the low-pressure stage of an R744 cascade system will typically be…
| Higher than the maximum permissible pressure in the low-pressure stage |
| The same as the high-pressure setting on the pressure switch |
| 27.5 bar g |
| The same as the pressure set on the relief valve |
242
Difficult
What is the correct definition of critical temperature?
| The temperature above which there are no distinct liquid and gaseous phases |
| The temperature at which, for certain substances, electrical resistance is zero |
| The temperature at which a substance changes from a gaseous to a solid state |
| The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid |
243
Difficult
In a supercritical system, under supercritical conditions, the working fluid in the gas cooler
| it loses heat as its temperature drops |
| loses heat at constant temperature and pressure |
| loses heat during a phase change |
| it loses heat when its pressure drops |
244
Difficult
R717 is highly corrosive to
| titanium |
| copper |
| aluminium |
| stainless steel |
245
Difficult
What is the effect of repeatedly opening the relief valve?
| The relief pressure drops |
| The valve will not open |
| The valve remains fully open continuously |
| The relief pressure rises |
246
Medium
Oil traps on the suction pipework are required:
| always before any rise in the pipeline. |
| before the safety valve. |
| at the inlet to each component of the refrigeration system. |
| before the compressor. |
247
Difficult
What is the relationship between the pressure (P) and temperature (T) of nitrogen at the start (1) and end (2) of the leak test?
| P2 = (P1 × T1)/T2 |
| P2 = T2/(P1 × T1) |
| P2 = (P1 × T2)/T1 |
| P2 = T1/(P1 × T2) |
248
Difficult
What is the recommended alarm level for fixed leak detection systems for R717?
| 5,000 ppm |
| 500 ppm |
| 500,000 ppm |
| 50,000 ppm |
249
Difficult
Why are compressors with a separate electric motor most commonly used in R717 (NH₃) refrigeration systems?
| To reduce the condensing pressure |
| Because compressors with a separate motor are cheaper |
| Because NH₃ reacts with the motor windings and hermetic compressors are not used |
| To increase the amount of refrigerant in the system |
250
Difficult
Which type of compressor is most commonly used in large ammonia systems?
| A reciprocating or screw compressor |
| Hermetic scroll |
| Diaphragm compressor |
| Rotary vane compressor |
251
Difficult
How is the capacity of a piston compressor regulated in NH₃ systems?
| Solely by adjusting the oil volume |
| By increasing the condensing pressure |
| By unloading the cylinders or changing the rotational speed |
| By reducing the refrigerant charge |
252
Difficult
How is the capacity of a screw compressor most commonly controlled?
| By closing the suction valve |
| By changing the type of oil |
| By adjusting the oil level |
| By using a slide valve |
253
Difficult
When is two-stage compression used in NH₃ systems?
| At very low vapour pressures and high pressure differentials |
| At small temperature differences |
| Only with water-cooled condensers |
| Exclusively in small systems |
254
Difficult
What is the advantage of two-stage compression over single-stage compression?
| No need for a separator |
| Lower efficiency |
| Higher energy consumption |
| Higher efficiency and lower discharge temperature |
255
Difficult
How does an evaporative condenser used in NH₃ systems work?
| Operates without a fan |
| It transfers heat only to the air |
| It does not require a water supply |
| It utilises the evaporation of water to increase cooling efficiency |
256
Difficult
What is the function of the liquid separator in an NH₃ system?
| It separates oil from the refrigerant |
| It prevents liquid from entering the compressor |
| Regulates the condensing pressure |
| Increases the discharge temperature |
257
Medium
When is there a refrigerant leak, even though the compressor is still running?
| When the suction pressure is low, superheat is high, subcooling is negligible and the temperature difference between the condenser and the expansion valve is small. |
| When the sight glass is full of liquid refrigerant and we observe a rise in the oil level in the compressor sump. |
| When we observe a rise in the refrigerant level in the liquid receiver and the subcooling increases. |
| When the condensing pressure and suction pressure rise, but there is no superheat. |
258
Difficult
What is the purpose of monitoring the liquid level in the separator?
| To control the condenser fan |
| To increase the oil volume |
| To maintain the correct refrigerant level and prevent the compressor from flooding |
| To reduce the condensing temperature |
259
Difficult
What is the role of the float switch in NH₃ systems?
| It regulates the condensation temperature |
| It controls the fan’s operation |
| It is used to detect leaks |
| It monitors the liquid level in the tank or separator |
260
Difficult
What is a thermosiphon in NH₃ systems?
| An oil circulation system utilising differences in pressure and temperature |
| A type of evaporator |
| A defrosting device |
| A type of safety valve |
261
Difficult
Why are oils that are immiscible with the refrigerant used in NH₃ systems?
| To reduce the pressure |
| Because the oil mixes only with water |
| Because NH₃ does not mix with most compressor oils |
| To increase the amount of refrigerant |
262
Difficult
What is the main function of an oil separator in NH₃ systems?
| To increase fan efficiency |
| To lower the condensation temperature |
| Removing moisture from the system |
| To separate the oil from the refrigerant and return the oil to the compressor |
263
Difficult
Which NH₃ system features direct evaporation of the refrigerant in the evaporator?
| Indirect system |
| Thermosiphon system |
| Direct expansion (DX) system |
| Glycol system |
264
Difficult
What is the characteristic feature of a flooded evaporator system?
| No separator is used |
| The evaporator is filled exclusively with vapour |
| The evaporator contains a large amount of liquid, which improves heat transfer |
| No level control is required |
265
Difficult
What is the main difference between a direct and an indirect system?
| In an indirect system, no compressor is used |
| In a direct system, there is no evaporator |
| In an indirect system, NH₃ flows directly into the space being cooled |
| In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load |
266
Medium
Which components of a refrigeration system can be classified as potential leak points (leaks) subject to regular leak tests?
| Hermetic compressors, liquid refrigerant tanks and liquid separators. |
| Parts of the system located on the high-pressure side (from the compressor up to and including the expansion valve). |
| Fittings, valves including their stems, seals – including those in replaceable filters and dryers, components exposed to vibration, and connections to measuring, control and safety devices. |
| All parts of the refrigeration unit that are connected to the suction side of the refrigeration system. |
267
Medium
What is the test pressure during the pressure leak test of the unit?
| According to the PN-EN 378 standard, at least 0.25 times the maximum permissible pressure for the system (PS). |
| The test pressure for leak testing is equivalent to the maximum operating pressure measured during the operation of the refrigeration unit. |
| The test pressure is determined by the person carrying out the leak test based on their experience. |
| The test pressure (maximum) is 30 bar. |
268
Medium
In which part of the refrigeration unit must the recommended leak test be carried out?
| The test must be carried out at all points on the refrigeration unit where there is a potential risk of refrigerant leakage. |
| The check should only be carried out at the connection points for measuring instruments (pressure switches, pressure gauges, temperature sensors). |
| The test must be carried out on the compressor shut-off valves, solenoid valves and filters. |
| The check must be carried out on all parts of the refrigeration system that are connected to the discharge side of the refrigeration circuit. |
269
Medium
When can a given unit be considered perfectly leak-tight?
| A given unit can be considered perfectly leak-tight if, during a leak test, the pressure remains constant, taking into account pressure changes caused by temperature variations. Any drop in pressure indicates a leak and requires the location of the leak to be identified. |
| A given device can be considered perfectly leak-tight when the pressure drop during the test does not exceed 0.1 bar. |
| A device can be considered perfectly leak-tight if gas bubbles appear when it is submerged in water. |
| The device in question is perfectly leak-tight when we have carried out a check using a permanently installed electronic detector. |
270
Medium
What does EU Regulation 1516/2007 cover?
| The Regulation sets out health and safety requirements for soldering work. |
| The Regulation concerns leak testing of stationary refrigeration, air-conditioning and heat pump equipment containing fluorinated greenhouse gases. The Regulation sets out the requirements for leak testing of such equipment. |
| The Regulation addresses the disposal of gases that contribute to the greenhouse effect. |
| The Regulation sets out requirements relating to brazing of refrigeration systems. |
271
Difficult
Which parts of refrigeration systems must be inspected on a mandatory and regular basis in accordance with EU Regulation 1516/2007?
| Only compressor connections, as these are subject to vibration. |
| Compressor connections, 2. connections on the liquid refrigerant tank |
| Fittings, 2. valves, 3. seals, 4. parts/components exposed to vibration, 5. connections at safety devices. |
| Connections on the condenser, as there is high pressure and the refrigerant is in liquid form |
272
Easy
What is superheat?
| It is the amount of heat required to increase the pressure. |
| It is the amount of heat required to cause the vapour formed from a liquid to become superheated. |
| It is the amount of heat required to turn a liquid into vapour. |
| It is the amount of heat required to heat a liquid. |
273
Difficult
In accordance with EU Regulation 1516/2007, there are several methods of leak testing. What are these methods called?
| We distinguish between direct and indirect methods of leak detection. |
| We distinguish between methods for quality control of supplied materials and leak testing methods that do not involve quality control of supplied materials. |
| We distinguish between physical and chemical methods. |
| We distinguish between quality control methods for supplied materials and electronic testing methods. |
274
Difficult
In accordance with EU Regulation 1516/2007, to whom can we entrust the responsibilities for leak testing of refrigeration systems?
| The test may only be carried out by a competent person with the relevant skills, who holds a certificate attesting to the necessary knowledge in this field. They must also hold a certificate for companies regarding the operation and maintenance of refrigeration equipment charged with F-gases. |
| The check may only be carried out by a person who has previously carried out such a check. |
| The check may be carried out by a specialist in leak testing. |
| The inspection may be carried out by a person employed and appointed by the owner of the installation. |
275
Difficult
In accordance with EU Regulation 1516/2007, what conditions must be met in order to carry out a leak test on refrigeration systems using ultraviolet (UV) light?
| A prerequisite for carrying out the inspection is holding the relevant authorisation for pressure testing issued by the UDT. |
| A prerequisite for carrying out a leak test using UV is that such a test is technically feasible. |
| A prerequisite for carrying out a leak test using UV is having the appropriate technical resources, the relevant materials supplied, and suitable safety goggles. |
| The manufacturer of the refrigeration equipment must confirm that the aforementioned UV method can be used. A UV leak test may be carried out by a qualified person who holds the relevant qualifications (certificate). |
276
Difficult
In accordance with EU Regulation 1516/2007, which leak testing methods are classified as direct leak testing methods?
| Detection of leaks using a handheld leak detector and/or a fixed leak detection system; 2. Detection of leaks using a special dye with UV-fluorescent properties; 3. Detection of leaks using a foaming solution. |
| Leak test using nitrogen with a tracer gas, an electronic detector and pressure measurement. |
| Leak test following the creation of a vacuum and leak detection using a foaming solution. |
| Leak testing by measuring pressure changes and the method of submerging the device/system in water. |
277
Difficult
In accordance with EU Regulation 1516/2007, which methods are classified as indirect leak testing methods?
| It utilises pressure and temperature measurements, as well as an ultrasonic method. |
| This method is based on electronic leak detection. |
| This method is based on the analysis of the following parameters: pressure, temperature, operating pressure, liquid level, oil leakage, etc. |
| Leak detection using a UV tracer. |
278
Medium
How should the pressure be increased during a pressure leak test?
| We increase the pressure as quickly as possible. |
| We increase the pressure gradually whilst checking for leaks, until the test pressure is reached, at a rate of no more than 2 bar/min |
| We increase the pressure in any way. |
| We increase the pressure at a rate of 10 bar/s. |
279
Medium
What electronic equipment should be used to carry out leak testing?
| Only using devices with verified measurement sensitivity. |
| Only with devices fitted with hot cathodes. |
| Only with devices fitted with an ‘Ion Pump’ sensor. |
| Only with devices fitted with an infrared detector. |
280
Medium
What documentation should be checked before starting a leak test?
| Check the operating instructions for the machine/equipment. |
| Check the time sheets of the staff responsible for the machinery/equipment. |
| Check the stock ledger (accounts). |
| The maintenance log and the machine/device operating instructions must be checked. |
281
Medium
What information must be recorded when drawing up the leak test report?
| The number of locations where leaks have occurred and the date of the inspection. |
| The method used to carry out the leak test, the number of faults, the method of repairing the faults, the time taken to work on the installation, and the cost of the repair. |
| The date of the inspection, a record of the occurrence of the leak, and a signature. |
| The date of the inspection, the number of faults (leaks), the location of the faults (leaks), the proposed method of rectifying the fault/defect (leak), attached documents and a signature. |
282
Medium
What pressure values should be used for the pressure leak test?
| At the discretion of the person authorised to carry out the pressure test. |
| The pressure for the leak test is 2–3 bar. |
| The pressure value for the leak test is 10–12 bar. |
| Use a pressure not exceeding the maximum permissible pressure for the system (PS). |
283
Medium
What is temperature slip?
| It involves an increase in temperature. |
| A specific temperature cannot be assigned to a given vapour pressure. There is a temperature difference between the start and end of evaporation. |
| A specific temperature corresponds to a given vapour pressure. |
| It involves a decrease in temperature. |
284
Difficult
What does a vacuum leak test involve?
| With the vacuum pump switched on, check whether the pressure in the system rises as a result of a leak. |
| After switching off the vacuum pump, we check whether the pressure in the system rises |
| With the vacuum pump running continuously, we are able to maintain the required vacuum level in the system. |
| If the pressure in the refrigeration system were to rise, we switch on the vacuum pump as required. |
285
Difficult
How often should leak tests be carried out on equipment containing 1.5 kg of R404A refrigerant (5.9 tonnes of CO₂ equivalent)?
| At least once every 12 months. |
| On initial commissioning. |
| Once every six months. |
| Only when servicing the unit. |
286
Difficult
How often should leak tests be carried out on equipment containing 7 kg of R404A refrigerant (27.45 tonnes of CO₂ equivalent)?
| Only when servicing the unit. |
| On initial commissioning. |
| Once every six months. |
| At least once every 12 months. |
287
Medium
In which appliances and systems is the installation of a permanent leak detection system required?
| In equipment and systems containing at least 5 tonnes of CO₂ equivalent. |
| In equipment and systems containing at least 500 tonnes of CO₂ equivalent. |
| In equipment and systems containing at least 50 tonnes of CO₂ equivalent. |
| In equipment and installations containing at least 30 kg of fluorinated greenhouse gases. |
288
Difficult
In accordance with Regulation (EU) 2024/573 of the European Parliament and of the Council, a fixed leak detection system is required when:
| The refrigeration equipment is operated in an enclosed space. |
| The installation of a fixed leak detection system is optional, but it helps to reduce the number of leak checks required on the equipment each year. |
| The refrigerant charge of the refrigeration equipment is at least 100 kg of ODS. |
| The charge of an F-gas refrigerant in a refrigeration unit is at least 500 tonnes of CO₂ equivalent. |
289
Difficult
Under Regulation (EC) No 1516/2007 and the F-gas Act, which leak detection methods may not be carried out by a person holding a Category E certificate?
| Visual leak inspection. |
| Leak testing using a fluorescent dye. |
| Leak detection using a foaming solution. |
| Measuring leaks using a handheld leak detector. |
290
Difficult
According to the current regulation, what sensitivity must a handheld leak detector have?
| 8 g/year. |
| 10 g/year. |
| 3 g/year. |
| 5 g/year. |
291
Medium
Which category of F-gas certificate (A1, A2, B, C, D, E) authorises the performance of leak tests on refrigeration equipment:
| Category E only. |
| Only categories A1 and A2. |
| Categories D and E. |
| All except category D. |
292
Difficult
Within what timeframe must a leak test be carried out on a stationary refrigeration system after a leak has been repaired, in accordance with EU Regulation 2024/573 on F-gases?
| Immediately after the repair. |
| Between 24 hours and 1 month after the repair. |
| At any time. |
| At the next periodic inspection. |
293
Difficult
At what intervals should leak tests be carried out on refrigeration equipment containing more than 500 tonnes of CO₂ equivalent of fluorinated greenhouse gases that does not have a leak detection system installed?
| Once every 6 months. |
| Once a month. |
| Once every 3 months. |
| Once every 12 months. |
294
Medium
Why is it advisable to subcool the liquid refrigerant?
| This is advisable because it allows a smaller condenser to be used (smaller heat exchange surface area). |
| This is advisable because it allows a smaller evaporator to be used (lower refrigerant temperature at the evaporator inlet). |
| This is advisable because it allows a smaller expansion valve to be used (less superheat at the valve). |
| This is advisable because it ensures that the liquid refrigerant, free of vapour bubbles, enters the expansion valve. |
295
Medium
What should be done following repairs to a leak in the refrigeration unit of a refrigerated trailer?
| The unit must be charged with an alternative refrigerant, started up, and the refrigerant parameters checked at the service valve located on the liquid receiver. |
| An invoice for the service work carried out must be issued as soon as possible. |
| You must enter the details into the equipment log (including the quantities of refrigerant recovered and used) and inform the Operator that an additional leak test must be carried out by a certified person within one month of the repair. |
| A visual inspection should be carried out only on bolted and soldered joints. |
296
Medium
Recovery of fluorinated greenhouse gases means:
| The reuse of fluorinated greenhouse gases following a basic purification process. |
| The final decommissioning and withdrawal from service or use of a product or piece of equipment containing fluorinated greenhouse gases. |
| The reprocessing of fluorinated greenhouse gases to achieve their specified standard properties. |
| The collection and storage of fluorinated greenhouse gases originating, for example, from machinery, equipment and containers. |
297
Medium
Who is authorised to recover refrigerant from stationary refrigeration equipment:
| The administrator of the operator’s account. |
| A service technician holding an F-gas certificate in the relevant category. |
| The owner of the installation. |
| The operator. |
298
Medium
Recovered refrigerants must be stored:
| In a cylinder that previously contained the same type of refrigerant. |
| In a specially adapted and labelled cylinder fitted with a two-way valve. |
| In any used refrigerant cylinder. |
| In any pressure vessel that has been officially certified. |
299
Medium
When should the recovery of fluorinated greenhouse gases be carried out:
| Only prior to the final disposal of equipment. |
| Before each leak test of the equipment. |
| Always during servicing and maintenance of equipment. |
| Before the final disposal of equipment and, where applicable, during its servicing and maintenance. |
300
Medium
What should be done if the refrigerant recovered from the system is contaminated, e.g. with acid, air or moisture?
| You should attempt to purify the mixture yourself using a dehydrating filter. |
| Such a mixture must be handed over to a specialist authorised company for regeneration or disposal. |
| Purify the mixture by passing it through a particulate filter and reuse it. |
| Add a special contaminant neutraliser to the mixture. |
301
Medium
What should be done if different types of refrigerants become mixed in a storage cylinder (container)?
| Send this mixture to a specialist authorised company to have it neutralised. |
| You should attempt to separate the mixture into its individual components. |
| Add a special refrigerant to the mixture. |
| The mixture should be purified by passing it through a filter-drain and reused. |
302
Medium
How does refrigerant recovery using the Push-Pull method work?
| This involves injecting nitrogen from the cylinder into the unit and expelling the liquid refrigerant from the unit. |
| This involves using a suction device (compressor) to ensure that the refrigerant, in liquid form, is transferred into the cylinder. |
| It involves using a recovery unit to draw (pull) the refrigerant vapour from the cylinder and then force it (push) into the low-pressure side of the system. |
| This involves the refrigerant being alternately drawn from the suction side and then from the discharge side of the refrigeration unit (compressor). |
303
Medium
What are the methods for managing waste refrigerant?
| Disposal, storage. |
| Recovery, disposal. |
| Recycling, regeneration, disposal. |
| Regeneration, recovery. |
304
Medium
The most advantageous method of managing waste refrigerant is:
| Storage. |
| Disposal. |
| Regeneration. |
| Recycling. |
305
Medium
The lower the evaporation temperature, ...
| ...the lower the refrigerant density, and the greater the cooling capacity of the compressor. |
| ...the greater the density of the refrigerant and the mass flow rate of the flowing refrigerant. |
| ...the lower the density of the refrigerant and the lower the mass of the flowing refrigerant. |
| …the greater the density of the refrigerant and the lower the mass flow rate of the refrigerant. |
306
Medium
How should pressure vessels (e.g. refrigerant cylinders) be marked?
| They should bear the manufacturer’s logo and the date of manufacture. |
| They should bear, amongst other things, information such as: the number of the standard applied to their design, construction and testing; the identification marks of the country of approval and the inspection body; the date of the acceptance test; and the manufacturer’s and operational marks. |
| It is irrelevant how pressure vessels should be marked. |
| They should bear only markings relating to weight and capacity. |
307
Medium
The recovery of refrigerants does not require the use of:
| Hoses with shut-off valves. |
| A refrigerant recovery station. |
| An electronic leak detector. |
| Scales with a measurement range suitable for the size of the cylinder being filled. |
308
Medium
What functions does the compressor perform in a refrigeration system?
| The compressor creates a vacuum on the suction side of the system |
| The compressor compresses ambient air and increases the pressure of the refrigerant. |
| The compressor draws in refrigerant vapour from the evaporator, compresses it, and then forces it into the condenser, raising the pressure to the required condensing pressure. |
| The compressor condenses the refrigerant. |
309
Easy
What is the compressor’s compression ratio?
| It is the amount of refrigerant that will be compressed in a single compressor cycle relative to the heat capacity. |
| It is the ratio of the suction pressure to the discharge pressure of the compressor (po/pk). |
| It is the ratio of the discharge pressure to the suction pressure of the compressor (pk/po). |
| It is the ratio of the discharge pressure to the effective capacity of the compressor (p/Vk). |
310
Medium
What is compressor flooding?
| A large amount of liquid refrigerant in the evaporator. |
| Flooding of the compressor due to rainfall. |
| Flooding the compression chamber with liquid refrigerant or oil. |
| Suction of liquid refrigerant into the compressor’s suction line. |
311
Medium
To what extent do we regulate the compressor motor’s rotational speed when using a frequency converter?
| Regulating the compressor motor speed is not the same as regulating the cooling capacity. |
| From approximately 30% to 90% of capacity. |
| Up to a maximum of 10 per cent. |
| Approximately from 30 to 75 Hz, which corresponds to around 60% to 150% of the cooling capacity. |
312
Easy
What is the theoretical displacement of a compressor?
| The displacement of a compressor is determined by the dimensions of the cylinder – its volume (cm³) |
| The displacement capacity of a compressor is expressed by the coefficient of performance (COP) |
| This is the volume of refrigerant that flows through a reciprocating compressor during a single piston cycle. |
| It is the volume of refrigerant delivered by a reciprocating compressor per unit of time, usually referred to by the manufacturer as the displacement. It depends on the compressor’s geometric dimensions and rotational speed. |
313
Medium
Why is it essential to observe the correct phase sequence for scroll compressors and screw compressors?
| Because this type of compressor has difficulty starting up if the phase sequence is changed. |
| Because the motor speed would decrease, and consequently the compressor’s capacity. |
| Because changing the phase sequence would reverse the direction of rotation of the compressor rotors, which could result in damage to the compressors. |
| Because these types of compressors are sensitive to voltage drops. |
314
Medium
The cycle of a two-stage vapour-compression refrigeration system should have, in each stage of the system:
| a compression ratio of less than 18. |
| a compression ratio of less than 8. |
| a compression ratio greater than 8. |
| a compression ratio of less than 6 |
315
Medium
Why is it necessary to seal the shafts in gland-sealed refrigeration compressors?
| Because it protects the compressor’s crankshaft bearing. |
| Because it ensures the bearing remains lubricated. |
| Because we need to prevent air from entering the compressor and we need to prevent refrigerant from leaking from the compressor. |
| Because it prevents oil leakage. |
316
Medium
When is the refrigerant sufficiently cooled?
| When the evaporator is covered in frost. |
| When the outlet from the condenser is cold. |
| When no vapour bubbles are observed forming in the liquid sight glass. |
| When the liquid distributors are warm. |
317
Medium
Why should the compressor crankcase be heated?
| Heating improves the dissolution of the refrigerant in the oil, which is beneficial for its viscosity. |
| Heating ensures that the lubricating oil is de-watered. |
| Heating keeps the lubricating oil in a liquid state. |
| Heating prevents the refrigerant from dissolving in the oil. |
318
Easy
What is the dead volume of a compressor?
| It is the space between the valve plate and the bottom dead centre of the piston. |
| This is the space between the side surface of the piston and the cylinder. |
| It is the space between the valve plate and the top of the piston. |
| This is the space between the bottom of the piston and the crankshaft cover. |
319
Medium
What are compressor sets?
| These are sets comprising several compressors connected in any configuration. |
| These are units consisting of two-stage compressors. |
| These consist of a larger number (several) of compressors connected in parallel and mounted on a common frame. |
| These are multiple (several) air-cooled condensers. |
320
Medium
What are the advantages of compressor units?
| These are inexpensive and easy-to-install units. |
| Easy modification of the system. |
| The ability to adjust the cooling capacity as required. |
| Space-saving and lower energy consumption. |
321
Medium
What do we mean by the ‘application range’ of a compressor?
| By this term, we mean the following parameters: the evaporation and condensation temperatures (to and tk), or the pressure values that determine the compressor’s application. |
| By this term, we mean the following parameters: compressor capacity, type of refrigerant, and the compressor’s geometric dimensions. |
| By this term, we mean that the compressor’s operating range is determined by the evaporation temperature ‘to’ during operation. |
| By this term, we mean that the compressor’s application range is determined by the evaporation temperature ‘to’ at a given ambient temperature. |
322
Medium
What are the basic functions of oil in a compressor?
| The oil seals any leaks that develop in the system. |
| The oil absorbs moisture from the refrigerant that enters the compressor. |
| The oil lubricates both the bearings and the sliding surfaces of the compressor components, and cools the compressor by transferring the heat generated during compression to the compressor’s outer casing. |
| The oil seals the gap between the piston and the cylinder. |
323
Medium
What are the most effective ways of regulating the compressor’s cooling capacity?
| Using an expansion valve. |
| By changing the compressor’s displacement, by varying the rotational speed, or by deactivating individual cylinders. |
| By partially covering the evaporator to reduce the heat exchange surface area. |
| By means of pressure control valves. |
324
Medium
What does compressor bypass control involve?
| Refrigerant in the form of cooled, high-pressure vapour is introduced into the suction line. |
| High-pressure liquid refrigerant is injected on the suction side of the compressor. |
| Hot, high-pressure refrigerant vapour is drawn in on the suction side of the compressor. |
| The bypass control is not used to regulate the compressor. |
325
Medium
What is the fundamental difference between hermetic and semi-hermetic compressors?
| The housing of a hermetic compressor and the compressor itself form a single unit. |
| Semi-hermetic compressors are characterised by the quiet operation of the entire unit. |
| Both types of compressors are disassemblable, and the difference lies in their varying capacities. |
| The casing of semi-hermetic compressors can be dismantled, whereas the casing of hermetic compressors cannot be dismantled. |
326
Medium
How does a scroll compressor work?
| It is a device fitted with two spirals. It is a type of positive displacement (volumetric) compressor in which compression takes place through the interaction of the two spirals. |
| It is a type of piston-type device. |
| It uses two screws to compress the refrigerant. |
| A scroll compressor is also known as a turbo compressor. |
327
Medium
What physical process takes place in the evaporator?
| It cools the refrigerant flowing through it. |
| The liquid refrigerant evaporates and a small amount of it becomes superheated. |
| It causes the refrigerant flowing through it to condense. |
| The medium flowing through the evaporator (glycol, water) evaporates, whilst the refrigerant condenses. |
328
Medium
What is the purpose of regulating the compressor’s capacity?
| Capacity control protects the compressor from low thermal loads. |
| It allows the cooling capacity to be adjusted to meet requirements. |
| It ensures that the cooling capacity is adjusted based on condensing temperatures. |
| It ensures adequate lubrication of the compressor. |
329
Medium
Why is inverter speed control suitable for refrigeration compressors?
| Inverter speed control reduces energy consumption only under natural conditions. |
| Inverter speed control enables continuous, smooth regulation of cooling capacity. |
| By reducing the speed of the refrigeration compressor motor, inverter speed control improves the return oil flow to the compressor. |
| Inverter speed control can be used with any type of compressor to ensure adequate lubrication. |
330
Medium
Does the suction gas temperature affect the cooling capacity of the compressor?
| It has a significant effect on performance. |
| It does, but only for reciprocating compressors. |
| It does, but only if the gas is deeply cooled. |
| Temperature has no effect on the compressor’s cooling capacity. |
331
Medium
In the case of compressor units fitted with an oil level control system, is it necessary to install the compressors at the same height?
| Only screw compressors. |
| No. |
| Only scroll compressors. |
| Yes. |
332
Medium
What functions does a compressor powered by the vehicle’s engine perform in a transport refrigeration system?
| This compressor creates a vacuum on the suction side of the system whilst the vehicle’s engine is switched off. |
| This compressor condenses the refrigerant whilst the vehicle is in motion. |
| The compressor compresses ambient air and increases the pressure of the refrigerant. |
| This compressor draws in refrigerant vapour from the evaporator, compresses it and then forces it into the condenser whilst the vehicle’s engine is running. |
333
Medium
Which natural fluids absorb heat from the refrigerant in the condenser?
| Water or air. |
| Water and an antifreeze mixture. |
| Air and CO2. |
| Ammonia |
334
Medium
What is the function of the condenser in refrigeration systems?
| Heat released in the regenerative heat exchanger is absorbed by the condenser. |
| The heat absorbed in the evaporator is then released into the environment via the condenser |
| The heat absorbed in the evaporator and transferred during the compression process is then released into the environment via the condenser. |
| Heat from the compressor is then released into the environment via the condenser. |
335
Medium
If the condensation temperature is higher than the critical point temperature of the refrigerant, condensation:
| will always occur regardless of the temperature. |
| will not occur. |
| will occur provided a specially designed condenser is used. |
| temperature has no effect on condensation. |
336
Medium
How does the subcooling of the refrigerant take place within a refrigeration system?
| Subcooling using an additional heat exchanger and liquid nitrogen. |
| Subcooling of the liquid refrigerant in the final section of the condenser. |
| Subcooling of the refrigerant using oil (dissolving the refrigerant in oil). |
| Subcooling using high-pressure hot vapour. |
337
Medium
What is the purpose of controlling the condenser fan speed?
| Condenser fan speed control safeguards against the maximum permissible condensing pressure. |
| Condenser fan speed control reduces energy efficiency. |
| Condenser fan speed control ensures that the condensing pressure is maintained at the correct level. |
| Dispersion of the refrigerant in the event of a system leak. |