F-Gas English Low GWP

Všetky otázky
HFC | Flammable | CO₂ | NH₃
Ľahké otázky | Stredne ťažké otázky | Ťažké otázky

1

Ťažká

Why do CO₂ refrigeration systems require special attention when separating liquid and oil?


CO₂ operates at high pressure, which increases the risk of compressor failure and leaks
CO₂ does not require lubrication, so separators are unnecessary
CO₂ is flammable, so separators cannot be used
CO₂ cannot be used in systems with sight glasses

2

Ťažká

What is the critical pressure of CO₂ (R744)?


Approximately 74 bar
Approximately 120 bar
Approximately 10 bar
Approximately 31 bar

3

Ťažká

What characterises the transcritical process in CO₂ systems?


The system operates above the critical point and the refrigerant does not condense in the conventional manner
It occurs only at low temperatures
It is irrelevant to the operation of the system
Conventional condensation occurs

4

Ťažká

What characterises the subcritical CO₂ process?


The conventional condensation process below the critical point
The absence of condensation
The absence of evaporation
Operation above the critical point

5

Ťažká

What is the log(p)-h diagram for CO₂ used for?


To detect leaks
To measure temperature
To regulate pressure
For analysing thermodynamic processes in a refrigeration system

6

Ťažká

What can be read from the log(p)-h graph?


Only the temperature
Pressure, enthalpy, temperature and state of the refrigerant
Only the amount of refrigerant
Only the humidity

7

Ťažká

What are CO₂ saturation tables used for?


To determine the oil quantity
To measure humidity
To regulate the compressor
To determine the relationship between temperature and pressure at saturation

8

Ťažká

What does the CO₂ saturation state mean?


A state of high pressure
Equilibrium between the liquid and vapour phases
A state in which the refrigerant is only a gas
Dry ice state

9

Ťažká

When can dry ice (solid CO₂) form?


In the event of a sudden drop in pressure and temperature below the triple point
During normal operation of the system
At high pressure
At high temperature

10

Ťažká

What risks are associated with the formation of dry ice in a CO₂ system?


No risk
Pressure reduction
Blocked pipes and system damage
Improved efficiency

11

Ťažká

How does the CO₂ pressure change as the temperature rises?


It decreases
It first decreases, then increases
It remains the same
Rises sharply

12

Ťažká

Why is understanding the log(p)-h graph particularly important for CO₂?


It only applies to NH₃
It doesn’t matter
As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis
It is only used for design purposes

13

Ťažká

What happens to CO₂ above the critical point?


It turns into a solid
It ceases to conduct heat
It turns into a liquid
It transitions to a supercritical state (no distinction between liquid and gas)

14

Ťažká

Why do CO₂ systems require precise pressure control?


They do not require control
Because there are no valves
Due to low pressures
Due to significant pressure changes with temperature fluctuations

15

Ťažká

What is the main characteristic of R744 (CO₂) refrigeration systems?


Low energy efficiency
Very high operating pressures
No need for regulation
Low operating pressures

16

Ťažká

What are the requirements for piping materials in CO₂ systems?


They may be made of any material
They must be able to withstand high pressures (e.g. high-grade steel)
It does not matter
They must be made exclusively from plastics

17

Ťažká

How does a booster system work in CO₂ installations?


It is used to store the refrigerant
It utilises two stages of compression (low and medium pressure) in a single system
It reduces the pressure in the evaporator
It reduces the amount of refrigerant

18

Ťažká

What is the function of high-pressure control valves in CO₂ systems?


They are used to store the refrigerant
They regulate oil flow
They lower the evaporator temperature
They control the pressure on the high-pressure side and optimise system operation

19

Ťažká

Why is pressure optimisation in CO₂ systems crucial?


It doesn’t matter
It enables the system to achieve maximum energy efficiency
It reduces the ambient temperature
It reduces the amount of refrigerant

20

Ťažká

What role do parallel-operating compressors play in CO₂ systems?


It does not matter
They increase energy consumption
They enable gas recovery from the medium-pressure stage and improve efficiency
They lower the ambient temperature

21

Ťažká

How does an ejector work in a CO₂ system?


It lowers the evaporator temperature
Stores the refrigerant
It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency
It increases the amount of refrigerant

22

Ťažká

What is the function of liquid ejectors in CO₂ systems?


They reduce atmospheric pressure
They assist with liquid recovery and improve evaporator feed
They increase the amount of oil
They raise the refrigerant temperature

23

Ťažká

What are the characteristics of partially flooded systems in CO₂ systems?


Low operating pressure
The presence of liquid in the evaporator, which improves heat transfer and efficiency
The absence of liquid in the evaporator
Lack of regulation

24

Ťažká

What is the main risk associated with static pressure in CO₂ systems?


A rise in pressure resulting from the refrigerant heating up whilst at rest
A decrease in refrigerant quantity
Increased efficiency
A drop in temperature

25

Ťažká

How can standstill pressure in CO₂ systems be reduced?


By shutting down the system completely
By increasing the temperature
By increasing the refrigerant charge
By using parallel compressors and external cooling systems

26

Ťažká

What does ‘stagnation’ of a refrigeration system mean in the context of CO₂?


A drop in temperature
Normal system operation
Improved efficiency
A lack of refrigerant flow, which can lead to increased pressure and safety risks

27

Ťažká

Why do CO₂ systems require more advanced automation than traditional systems?


Due to low pressures
Because there are no valves
They do not require automation
Due to the need for precise control of pressure and temperature

28

Ťažká

Which safety class applies to R744?


A2
A3
A1
B2L

29

Ťažká

In an R744 system operating in supercritical mode, the refrigerant entering the evaporator expansion valve is...


A two-phase mixture at intermediate pressure
Saturated vapour at intermediate pressure
A subcooled liquid
A supercritical fluid

30

Ťažká

In R744 supercritical systems, the gas cooler outlet valve controls:


The pressure in the gas cooler
The gas cooler fans
The inlet temperature to the gas cooler
The outlet temperature of the gas cooler

31

Ťažká

What is the main reason for using K65 copper tubing in some R744 systems?


They can withstand higher pressures
They come in a wider range of diameters
They bend easily
They have good low-temperature performance

32

Ťažká

Which of the following statements is correct regarding the installation of Schrader valves?


All Schrader valve cores are suitable for all refrigerants
When brazing the valve body to the system, the core must be removed, then refitted and tightened to the correct torque
Hydrocarbons leak through Schrader valves
Schrader valves must not be used in R744 systems

33

Ťažká

Which refrigerant can be detected using phenolphthalein paper?


R1234ze
R1270
R744
R717

34

Ťažká

How does a refrigerant shortage affect the high-pressure side of the system (without discharge pressure regulation)?


Discharge pressure will be higher, and the degree of subcooling will be lower
The discharge pressure will be lower, and the subcooling will be lower
Discharge pressure will be lower, subcooling will be higher
Discharge pressure will be higher, and the degree of subcooling will be higher

35

Ťažká

What is the benefit of using helium as a tracer gas in nitrogen during a pressure test?


It has smaller molecules and diffuses more easily
It is non-flammable
It has a higher pressure than pure nitrogen
It has a distinct odour

36

Ťažká

Why should an R744 system that has been drained be initially charged with the refrigerant in gaseous form?


To prevent the formation of dry ice
To prevent the drain valve from opening
To ensure that R744 is charged slowly
To prevent damage to the compressor

37

Ťažká

If an R744 system contains moisture because it has not been properly drained, what is the likely consequence?


Excessively high discharge pressure
The formation of hydrogen fluoride, which will decompose into hydrofluoric acid and damage the compressor
Reduced cooling capacity
The formation of carbonic acid, which will cause damage to the system

38

Ťažká

The pressure of R744 at a saturation temperature of 20 °C is approx.


14 bar g
25 bar g
90 bar g
56 bar g

39

Ťažká

At an ambient temperature of 25°C, the standby pressure in the low-pressure stage of an R744 cascade system will typically be…


The same as the pressure set on the relief valve
27.5 bar g
The same as the high-pressure setting on the pressure switch
Higher than the maximum permissible pressure in the low-pressure stage

40

Ťažká

What is the correct definition of critical temperature?


The temperature above which there are no distinct liquid and gaseous phases
The temperature at which a substance changes from a gaseous to a solid state
The temperature at which, for certain substances, electrical resistance is zero
The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid

41

Ťažká

In a supercritical system, under supercritical conditions, the working fluid in the gas cooler


loses heat at constant temperature and pressure
it loses heat when its pressure drops
loses heat during a phase change
it loses heat as its temperature drops