F-Gas English Low GWP

All questions
HFC | Flammable | CO₂ | NH₃
Easy questions | Medium questions | Difficult questions

1

Difficult

Why do CO₂ refrigeration systems require special attention when separating liquid and oil?


CO₂ does not require lubrication, so separators are unnecessary
CO₂ operates at high pressure, which increases the risk of compressor failure and leaks
CO₂ cannot be used in systems with sight glasses
CO₂ is flammable, so separators cannot be used

2

Difficult

What is the critical pressure of CO₂ (R744)?


Approximately 120 bar
Approximately 74 bar
Approximately 31 bar
Approximately 10 bar

3

Difficult

What characterises the transcritical process in CO₂ systems?


It occurs only at low temperatures
It is irrelevant to the operation of the system
The system operates above the critical point and the refrigerant does not condense in the conventional manner
Conventional condensation occurs

4

Difficult

What characterises the subcritical CO₂ process?


The conventional condensation process below the critical point
The absence of condensation
Operation above the critical point
The absence of evaporation

5

Difficult

What is the log(p)-h diagram for CO₂ used for?


For analysing thermodynamic processes in a refrigeration system
To regulate pressure
To measure temperature
To detect leaks

6

Difficult

What can be read from the log(p)-h graph?


Only the humidity
Pressure, enthalpy, temperature and state of the refrigerant
Only the temperature
Only the amount of refrigerant

7

Difficult

What are CO₂ saturation tables used for?


To determine the relationship between temperature and pressure at saturation
To regulate the compressor
To determine the oil quantity
To measure humidity

8

Difficult

What does the CO₂ saturation state mean?


Dry ice state
A state in which the refrigerant is only a gas
Equilibrium between the liquid and vapour phases
A state of high pressure

9

Difficult

When can dry ice (solid CO₂) form?


At high pressure
In the event of a sudden drop in pressure and temperature below the triple point
During normal operation of the system
At high temperature

10

Difficult

What risks are associated with the formation of dry ice in a CO₂ system?


Pressure reduction
Improved efficiency
No risk
Blocked pipes and system damage

11

Difficult

How does the CO₂ pressure change as the temperature rises?


It remains the same
It first decreases, then increases
It decreases
Rises sharply

12

Difficult

Why is understanding the log(p)-h graph particularly important for CO₂?


It is only used for design purposes
It only applies to NH₃
As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis
It doesn’t matter

13

Difficult

What happens to CO₂ above the critical point?


It ceases to conduct heat
It turns into a solid
It turns into a liquid
It transitions to a supercritical state (no distinction between liquid and gas)

14

Difficult

Why do CO₂ systems require precise pressure control?


Due to low pressures
Because there are no valves
Due to significant pressure changes with temperature fluctuations
They do not require control

15

Difficult

What is the main characteristic of R744 (CO₂) refrigeration systems?


Very high operating pressures
No need for regulation
Low operating pressures
Low energy efficiency

16

Difficult

What are the requirements for piping materials in CO₂ systems?


They must be made exclusively from plastics
They must be able to withstand high pressures (e.g. high-grade steel)
It does not matter
They may be made of any material

17

Difficult

How does a booster system work in CO₂ installations?


It reduces the pressure in the evaporator
It reduces the amount of refrigerant
It is used to store the refrigerant
It utilises two stages of compression (low and medium pressure) in a single system

18

Difficult

What is the function of high-pressure control valves in CO₂ systems?


They regulate oil flow
They are used to store the refrigerant
They control the pressure on the high-pressure side and optimise system operation
They lower the evaporator temperature

19

Difficult

Why is pressure optimisation in CO₂ systems crucial?


It enables the system to achieve maximum energy efficiency
It doesn’t matter
It reduces the amount of refrigerant
It reduces the ambient temperature

20

Difficult

What role do parallel-operating compressors play in CO₂ systems?


They enable gas recovery from the medium-pressure stage and improve efficiency
They increase energy consumption
They lower the ambient temperature
It does not matter

21

Difficult

How does an ejector work in a CO₂ system?


It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency
It lowers the evaporator temperature
It increases the amount of refrigerant
Stores the refrigerant

22

Difficult

What is the function of liquid ejectors in CO₂ systems?


They assist with liquid recovery and improve evaporator feed
They raise the refrigerant temperature
They increase the amount of oil
They reduce atmospheric pressure

23

Difficult

What are the characteristics of partially flooded systems in CO₂ systems?


Low operating pressure
The presence of liquid in the evaporator, which improves heat transfer and efficiency
Lack of regulation
The absence of liquid in the evaporator

24

Difficult

What is the main risk associated with static pressure in CO₂ systems?


A decrease in refrigerant quantity
Increased efficiency
A rise in pressure resulting from the refrigerant heating up whilst at rest
A drop in temperature

25

Difficult

How can standstill pressure in CO₂ systems be reduced?


By shutting down the system completely
By increasing the temperature
By increasing the refrigerant charge
By using parallel compressors and external cooling systems

26

Difficult

What does ‘stagnation’ of a refrigeration system mean in the context of CO₂?


Improved efficiency
A drop in temperature
Normal system operation
A lack of refrigerant flow, which can lead to increased pressure and safety risks

27

Difficult

Why do CO₂ systems require more advanced automation than traditional systems?


Due to low pressures
They do not require automation
Due to the need for precise control of pressure and temperature
Because there are no valves

28

Difficult

Which safety class applies to R744?


A1
B2L
A2
A3

29

Difficult

In an R744 system operating in supercritical mode, the refrigerant entering the evaporator expansion valve is...


A subcooled liquid
A supercritical fluid
Saturated vapour at intermediate pressure
A two-phase mixture at intermediate pressure

30

Difficult

In R744 supercritical systems, the gas cooler outlet valve controls:


The inlet temperature to the gas cooler
The pressure in the gas cooler
The gas cooler fans
The outlet temperature of the gas cooler

31

Difficult

What is the main reason for using K65 copper tubing in some R744 systems?


They come in a wider range of diameters
They can withstand higher pressures
They have good low-temperature performance
They bend easily

32

Difficult

Which of the following statements is correct regarding the installation of Schrader valves?


Hydrocarbons leak through Schrader valves
All Schrader valve cores are suitable for all refrigerants
Schrader valves must not be used in R744 systems
When brazing the valve body to the system, the core must be removed, then refitted and tightened to the correct torque

33

Difficult

Which refrigerant can be detected using phenolphthalein paper?


R744
R1270
R1234ze
R717

34

Difficult

How does a refrigerant shortage affect the high-pressure side of the system (without discharge pressure regulation)?


Discharge pressure will be lower, subcooling will be higher
Discharge pressure will be higher, and the degree of subcooling will be lower
The discharge pressure will be lower, and the subcooling will be lower
Discharge pressure will be higher, and the degree of subcooling will be higher

35

Difficult

What is the benefit of using helium as a tracer gas in nitrogen during a pressure test?


It has a distinct odour
It has smaller molecules and diffuses more easily
It has a higher pressure than pure nitrogen
It is non-flammable

36

Difficult

Why should an R744 system that has been drained be initially charged with the refrigerant in gaseous form?


To ensure that R744 is charged slowly
To prevent damage to the compressor
To prevent the formation of dry ice
To prevent the drain valve from opening

37

Difficult

If an R744 system contains moisture because it has not been properly drained, what is the likely consequence?


The formation of hydrogen fluoride, which will decompose into hydrofluoric acid and damage the compressor
Reduced cooling capacity
Excessively high discharge pressure
The formation of carbonic acid, which will cause damage to the system

38

Difficult

The pressure of R744 at a saturation temperature of 20 °C is approx.


14 bar g
56 bar g
25 bar g
90 bar g

39

Difficult

At an ambient temperature of 25°C, the standby pressure in the low-pressure stage of an R744 cascade system will typically be…


The same as the high-pressure setting on the pressure switch
The same as the pressure set on the relief valve
27.5 bar g
Higher than the maximum permissible pressure in the low-pressure stage

40

Difficult

What is the correct definition of critical temperature?


The temperature at which a substance changes from a gaseous to a solid state
The temperature above which there are no distinct liquid and gaseous phases
The temperature at which, for certain substances, electrical resistance is zero
The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid

41

Difficult

In a supercritical system, under supercritical conditions, the working fluid in the gas cooler


loses heat during a phase change
it loses heat as its temperature drops
it loses heat when its pressure drops
loses heat at constant temperature and pressure