F-Gas English Low GWP

All questions
HFC | Flammable | CO₂ | NH₃
Easy questions | Medium questions | Difficult questions

1

Difficult

What is the main difference between a dry evaporator and a flooded evaporator?


A dry evaporator has a lower operating pressure than a flooded one
A dry evaporator does not require an expansion valve, whereas a flooded one does
A dry evaporator allows the entire refrigerant to evaporate in the pipe upstream of the compressor; in a flooded evaporator, part of the refrigerant remains in a liquid state within the evaporator
A dry evaporator is filled with refrigerant liquid, whilst a flooded evaporator is filled with gas

2

Difficult

What is the typical pressure in deep-freezing systems (below −40 °C) for an evaporator in a system using R717?


Atmospheric pressure, approximately 1 bar
A pressure varying between 10 and 20 bar
Positive pressure, in the range of 5–10 bar
Negative pressure (vacuum), below 0 bar

3

Difficult

Why are PFAS substances formed as a result of the decomposition of certain F-gases problematic?


They are persistent, accumulate in the environment and may be toxic
They cause rapid cooling of the atmosphere
They are readily biodegradable, so they only pollute the environment for a short time
They are climate-neutral

4

Difficult

What is the basic requirement when charging a system with R717 (NH₃)?


Charging should take place in a well-ventilated area using appropriate personal protective equipment
Charging must only take place at temperatures below 0°C
Charging can be carried out without personal protective equipment
NH₃ can be charged together with air

5

Difficult

How should oil be handled in systems using R717?


The oil does not require any monitoring
Oil has no effect on the system’s operation
Oil can be mixed with any refrigerant
The oil should be checked regularly and any excess removed from the lower parts of the units to prevent reduced heat transfer and leaks

6

Difficult

What is the correct procedure for recovering R717 from a system?


The gas can be released into the atmosphere
Recovery is not required
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
The refrigerant can be drained into the sewer system

7

Difficult

How should R717 (NH₃) be stored?


In any open containers
In unmarked plastic containers
In sealed, labelled containers, in a cool and well-ventilated place
Near heat sources

8

Difficult

What should be done in the event of R717 contamination?


Add water to dilute it
Release into the atmosphere
The refrigerant must be purified or sent for disposal in accordance with regulations
Continue to use without restriction

9

Difficult

What is the main hazard associated with an R717 leak during maintenance work?


Toxic to humans and may cause chemical burns
No risk whatsoever
Damage to electrical equipment only
Increased cooling efficiency

10

Difficult

What action should be taken if an NH₃ leak is detected?


Evacuate personnel immediately and remove the source of the leak, if it is safe to do so
Ignore it and carry on working
Increase the pressure in the system
Close your eyes and carry on working

11

Difficult

What role do scrubbers play in NH₃ systems?


Neutralises ammonia through absorption in a liquid (e.g. water)
They increase the pressure in the system
They store the refrigerant
They are used to measure temperature

12

Difficult

How should the system be prepared before filling with R717?


There is no need to check it
The pressure must be increased above the standard level
Check for leaks, remove air and moisture, and create a vacuum
Simply start it up

13

Difficult

What are the transport requirements for R717?


Must be transported in suitable, labelled containers in accordance with ADR regulations
It can be transported without labelling
Transport is not subject to regulations
It can be transported in open containers

14

Difficult

What personal protective equipment is required when working with NH₃?


Workwear only
Only a safety helmet
Safety goggles, gloves and respiratory protective equipment
No requirements

15

Difficult

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 mixes very well with compressor oil and easily returns to the compressor
R717 does not mix with compressor oil, so the oil remains in the system on the low-pressure side as a layer beneath the R717
In an R717 system, a return oil line cannot be used because the oil is too hot
R717 does not mix with compressor oil, so the oil remains in the system on the high-pressure side as a layer above the R717

16

Difficult

Which system may require manual oil recovery?


An R717 system
R744 cascade system
Supercritical ‘booster’ system using R744
Secondary system using R744

17

Difficult

Which refrigerant is lighter than air?


R744
R717
R1234ze
R1270

18

Difficult

R717 is highly corrosive to


aluminium
titanium
copper
stainless steel

19

Difficult

What is the effect of repeatedly opening the relief valve?


The valve will not open
The valve remains fully open continuously
The relief pressure rises
The relief pressure drops

20

Difficult

What is the relationship between the pressure (P) and temperature (T) of nitrogen at the start (1) and end (2) of the leak test?


P2 = T2/(P1 × T1)
P2 = (P1 × T1)/T2
P2 = (P1 × T2)/T1
P2 = T1/(P1 × T2)

21

Difficult

What is the recommended alarm level for fixed leak detection systems for R717?


500 ppm
50,000 ppm
5,000 ppm
500,000 ppm

22

Difficult

Why are compressors with a separate electric motor most commonly used in R717 (NH₃) refrigeration systems?


Because NH₃ reacts with the motor windings and hermetic compressors are not used
Because compressors with a separate motor are cheaper
To reduce the condensing pressure
To increase the amount of refrigerant in the system

23

Difficult

Which type of compressor is most commonly used in large ammonia systems?


A reciprocating or screw compressor
Hermetic scroll
Diaphragm compressor
Rotary vane compressor

24

Difficult

How is the capacity of a piston compressor regulated in NH₃ systems?


By reducing the refrigerant charge
By unloading the cylinders or changing the rotational speed
By increasing the condensing pressure
Solely by adjusting the oil volume

25

Difficult

How is the capacity of a screw compressor most commonly controlled?


By using a slide valve
By closing the suction valve
By adjusting the oil level
By changing the type of oil

26

Difficult

When is two-stage compression used in NH₃ systems?


Only with water-cooled condensers
Exclusively in small systems
At small temperature differences
At very low vapour pressures and high pressure differentials

27

Difficult

What is the advantage of two-stage compression over single-stage compression?


Higher energy consumption
No need for a separator
Higher efficiency and lower discharge temperature
Lower efficiency

28

Difficult

How does an evaporative condenser used in NH₃ systems work?


It does not require a water supply
It utilises the evaporation of water to increase cooling efficiency
Operates without a fan
It transfers heat only to the air

29

Difficult

What is the function of the liquid separator in an NH₃ system?


Regulates the condensing pressure
It prevents liquid from entering the compressor
It separates oil from the refrigerant
Increases the discharge temperature

30

Difficult

What is the purpose of monitoring the liquid level in the separator?


To control the condenser fan
To reduce the condensing temperature
To maintain the correct refrigerant level and prevent the compressor from flooding
To increase the oil volume

31

Difficult

What is the role of the float switch in NH₃ systems?


It regulates the condensation temperature
It controls the fan’s operation
It monitors the liquid level in the tank or separator
It is used to detect leaks

32

Difficult

What is a thermosiphon in NH₃ systems?


An oil circulation system utilising differences in pressure and temperature
A defrosting device
A type of evaporator
A type of safety valve

33

Difficult

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


Because NH₃ does not mix with most compressor oils
Because the oil mixes only with water
To increase the amount of refrigerant
To reduce the pressure

34

Difficult

What is the main function of an oil separator in NH₃ systems?


Removing moisture from the system
To increase fan efficiency
To separate the oil from the refrigerant and return the oil to the compressor
To lower the condensation temperature

35

Difficult

Which NH₃ system features direct evaporation of the refrigerant in the evaporator?


Direct expansion (DX) system
Thermosiphon system
Glycol system
Indirect system

36

Difficult

What is the characteristic feature of a flooded evaporator system?


No level control is required
No separator is used
The evaporator is filled exclusively with vapour
The evaporator contains a large amount of liquid, which improves heat transfer

37

Difficult

What is the main difference between a direct and an indirect system?


In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load
In an indirect system, NH₃ flows directly into the space being cooled
In a direct system, there is no evaporator
In an indirect system, no compressor is used