1

Ťažká

What is the main difference between a dry-expansion and a flooded evaporator?


A dry-expansion evaporator is filled with liquid, a flooded one with vapour
A dry-expansion evaporator always has a lower pressure than a flooded one
In a dry-expansion evaporator the refrigerant completely evaporates and is superheated in the evaporator; in a flooded one part of the refrigerant remains liquid (incomplete evaporation, no superheat)
A dry-expansion evaporator needs no expansion valve, a flooded one does

2

Ťažká

What is the typical pressure in the evaporator of an R717 deep-freeze system (below −40 °C)?


Atmospheric pressure, approx. 1 bar abs
Positive pressure of 5–10 bar
Positive pressure of 10–20 bar
Below atmospheric (approx. 0.7 bar abs at −40 °C)

3

Ťažká

How is oil managed in R717 systems?


Oil can be mixed with any refrigerant
Oil collecting at the lowest points of vessels is regularly checked and drained, because it impairs heat transfer
Oil requires no monitoring
Oil has no effect on system operation

4

Ťažká

What should be done with contaminated R717?


Continue to use it without restriction
Release it into the atmosphere
Purify it or send it for disposal in accordance with regulations
Dilute it with water and reuse it

5

Ťažká

What should be done if an NH₃ leak is detected?


Increase the pressure in the system
Carry on working wearing a dust mask
Carry on working with the room door open
Evacuate people immediately and raise the alarm; stop the leak only if it is safe to do so and with suitable PPE (respiratory protection)

6

Ťažká

What role do scrubbers play in NH₃ systems?


They store the refrigerant
They are used to measure temperature
They increase the pressure in the system
Neutralise ammonia through absorption in a liquid (e.g. water)

7

Ťažká

How should the system be prepared before filling with R717?


Check for leaks, remove air and moisture, and create a vacuum
There is no need to check it
Simply start it up
The pressure must be increased above the standard level

8

Ťažká

What are the transport requirements for R717?


It can be carried without labelling
It can be carried in open containers
It must be carried in suitable, labelled packagings in accordance with ADR (UN 1005, class 2, code 2TC)
Transport is not regulated

9

Ťažká

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 does not mix with the oil; the oil, being heavier than liquid NH₃, collects beneath it at the lowest points (mainly on the low-pressure side)
An oil return line cannot be used in R717 systems because the oil is too hot
R717 mixes very well with the oil, which easily returns to the compressor
R717 does not mix with the oil; the oil collects on the high-pressure side above the R717

10

Ťažká

Which refrigerant can be detected with phenolphthalein paper?


R717
R1270
R744
R1234ze(E)

11

Ťažká

Which system may require manual oil recovery?


R744 cascade system
An R717 system
Supercritical ‘booster’ system using R744
Secondary system using R744

12

Ťažká

Which refrigerant is lighter than air?


R717
R744
R1234ze(E)
R1270

13

Ťažká

R717 is highly corrosive to:


aluminium
titanium
stainless steel
copper (and its alloys)

14

Ťažká

What is the recommended pre-alarm level for fixed leak detection systems for R717?


5,000 ppm
500,000 ppm
500 ppm
50,000 ppm

15

Ťažká

Why are compressors with a separate motor (open type) mostly used in R717 systems?


Because they are cheaper
To increase the refrigerant charge
To lower the condensing pressure
Because NH₃ attacks copper motor windings, so hermetic compressors with conventional windings are not used

16

Ťažká

Which type of compressor is most commonly used in large ammonia systems?


Diaphragm compressor
Rotary vane compressor
A reciprocating or screw compressor
Hermetic scroll

17

Ťažká

How is the capacity of a piston compressor regulated in NH₃ systems?


By increasing the condensing pressure
Solely by adjusting the oil volume
By reducing the refrigerant charge
By unloading the cylinders or changing the rotational speed

18

Ťažká

How is the capacity of a screw compressor most commonly controlled?


By using a slide valve
By adjusting the oil level
By closing the suction valve
By changing the type of oil

19

Ťažká

When is two-stage compression used in NH₃ systems?


At low evaporating temperatures (pressures) and high pressure ratios
Only in small systems
Only with water-cooled condensers
At small temperature differences

20

Ťažká

What is the advantage of two-stage compression over single-stage compression?


Higher energy consumption
Higher efficiency and lower discharge temperature
No need for a separator
Lower efficiency

21

Ťažká

How does an evaporative condenser used in NH₃ systems work?


It utilises the evaporation of water to increase cooling efficiency
It transfers heat only to the air
Operates without a fan
It does not require a water supply

22

Ťažká

What is the function of the liquid separator in an NH₃ system?


Increases the discharge temperature
It prevents liquid from entering the compressor
It separates oil from the refrigerant
Regulates the condensing pressure

23

Ťažká

What is the purpose of monitoring the liquid level in the separator?


To maintain the correct refrigerant level and prevent the compressor from flooding
To control the condenser fan
To increase the oil volume
To reduce the condensing temperature

24

Ťažká

What is the role of the float switch in NH₃ systems?


It controls the fan’s operation
It is used to detect leaks
It monitors the liquid level in the tank or separator
It regulates the condensation temperature

25

Ťažká

What is a thermosyphon in NH₃ systems?


A defrosting device
An oil circulation pump
A type of safety valve
A system with gravity-driven (natural) circulation of liquid refrigerant caused by density differences, used e.g. for screw compressor oil cooling

26

Ťažká

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


Because the oil mixes only with water
To increase the amount of refrigerant
To reduce the pressure
Because NH₃ does not mix with most compressor oils

27

Ťažká

What is the main function of an oil separator in NH₃ systems?


Removing moisture from the system
To increase fan efficiency
To lower the condensation temperature
To separate the oil from the refrigerant and return the oil to the compressor

28

Ťažká

In which NH₃ system does the refrigerant evaporate completely with superheat in the evaporator, fed by an expansion valve?


A glycol system
A pumped liquid-recirculation system
A direct-expansion (DX) system
An indirect system

29

Ťažká

What is the characteristic feature of a flooded evaporator system?


The evaporator is filled exclusively with vapour
No separator is used
The evaporator contains a large amount of liquid, which improves heat transfer
No level control is required

30

Ťažká

What is the main difference between a direct and an indirect system?


In an indirect system, NH₃ flows directly into the space being cooled
In an indirect system, no compressor is used
In a direct system, there is no evaporator
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load